Thermocouple Converter KFD0-TT-1 895

Thermocouple Converter KFD0-TT-1

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 895
Цена: 2 273 630 Руб
Купить

Цены носят информационный характер и не являются публичной офертой. Точную цену и срок поставки подтвердит менеджер при оформлении заявки

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • 1-channel signal conditioner
  • 24 V DC supply (loop powered)
  • Thermocouple input
  • Output 4 mA ... 20 mA
  • Internal cold junction compensation
  • Sensor breakage detection
  • DIP switch selectable ranges
Параметр Значение
Общие характеристики
Артикул 895
Control elements DIP-switch rotary switch
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Degree of protection IP20
Connection screw terminals
Mass approx. 150 g
Rated voltage 12 ... 35 V DC loop powered
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Current lead monitoring ON: ≤ 15 nA; OFF: ≤ 1 nA
Measurement range span 4 ... 100 mV, zero point -12 ... 60 mV , both adjustable
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Labeling space for labeling at the front
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Rise time 250 ms
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Power dissipation 0.4 W
Fault signal downscaling ≤ 3 mA , upscaling ≥ 22 mA
Configuration via DIP switches via rotary switch
Insulation coordination EN 50178
Galvanic isolation EN 50178
Connection side control side
Load (U -12 V) / 0.02 A
Input/Output safe isolation according to EN 50178, rated insulation voltage 253 V
Signal type Analog input
Lead resistance max. 100 Ω per line
After calibration 0.1 % of full-scale value ± 1 K for the cold junction
Temperature effect temperature deviation 0.015 % of the span/K or 1.5 µV/K cold junction ± 2 K (calibrated at T = 20 °C (68 °F))
Current output 4 ... 20 mA , limited to ≤ 35 mA
Influence of supply voltage 6.5 ppm/V
Characteristic curve the output voltage is linearly proportionate to the input voltage (not to temperature)