  • 1-channel signal conditioner
  • 24 V DC supply (Power Rail)
  • Strain gauge input (full or half bridge)
  • Output 0 mA ... ± 20 mA or 0 V ... ± 10 V
  • 2 relay contact outputs
  • Programmable high/low alarm
  • Configurable by PACTware or keypad
  • RS-485 interface
  • Line fault detection (LFD)
Параметр Значение
Общие характеристики
Артикул 48360
Control elements Control panel
Ripple within the supply tolerance
UL approval E223772
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Degree of protection IP20
Connection screw terminals
Mass approx. 250 g
Rated voltage 20 ... 35 V DC
Power consumption max. 3 W
Type RS-485
Sensor supply 1 ... 5 V
Analog voltage output 0 ... ± 10 V; output resistance 500 Ω (bridge between terminal 7 and 9)
Analog current output 0 ... ± 20 mA or 4 ... 20 mA; load 0 ... 550 Ω (terminals 7 and 8)
Electromagnetic compatibility NE 21:2006
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mechanical life 2 x 10 switching cycles
Labeling space for labeling at the front
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Contact loading 253 V AC/2 A/500 VA/cos φ min. 0.7; 40 V DC/2 A resistive load
Input I Signal, analog
Output III Analog output
Display elements LEDs , display
Configuration via operating buttons via PACTware
Directive 2004/108/EC EN 61326-1:2006
Short-circuit current 50 mA
Connection side control side
Reaction time 300 ... 850 ms
Load max. 550 Ω
Input resistance > 1 MΩ for voltage measurement
Line fault detection downscale -21.5 mA (-10.75 V) or 2 mA (1 V), upscale 21.5 mA (10.75 V)
Directive 2006/95/EC EN 61010-1:2010
Signal type Analog input
Open circuit voltage/short-circuit current 18 V / 5 mA
Programming interface programming socket
Active/Passive I > 4 mA/I < 1.5 mA
Output I, II Relay output
Current range -20 ... 20 mA
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Input I/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Lead resistance max. 25 Ω per line
Resolution/accuracy ≤ ± 0.05 % incl. non-linearity and hysteresis
Input signal -100 ... 100 mV
Programmable Tare 0 ... 500 % of span
Input II, III tare adjustment, calibration and zero
Collective error message Power Rail
Temperature effect ≤ ± 0.01 %/K
Output I, II against eachother reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output III/Input II, III not available
Output III/Programming socket not available
Other circuits from each other functional insulation, rated insulation voltage 50 V