  • 1-channel signal conditioner
  • 24 V DC supply (Power Rail)
  • Thermocouple, RTD, potentiometer or voltage input
  • Redundant TC input
  • Current output 0/4 mA ... 20 mA
  • 2 relay contact outputs
  • Configurable by PACTware or keypad
  • Line fault (LFD) and sensor burnout detection
  • Up to SIL 2 acc. to IEC 61508/IEC 61511
Параметр Значение
Общие характеристики
Артикул 48361
Control elements Control panel
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Degree of protection IP20
Connection screw terminals
Mass 300 g
Rated voltage 20 ... 30 V DC
Electromagnetic compatibility NE 21:2007
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Potentiometer 0.8 ... 20 kΩ
Mechanical life 5 x 10 switching cycles
Labeling space for labeling at the front
Rated current approx. 100 mA
Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Output III Analog current output
Safety Integrity Level (SIL) SIL 2
Display elements LEDs , display
Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43)
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Configuration via operating buttons via PACTware
Directive 2014/35/EU EN 61010-1:2010
Voltage 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV
Connection side control side
Load max. 650 Ω
Input resistance ≥ 250 kΩ (0 ... 10 V) min. 1 MΩ (0 ... 1 V, -100 ... 100 mV)
Measuring current approx. 400 µA
Open loop voltage max. 24 V DC
Signal type Analog input
Programming interface programming socket
Output I, II relay
Current range 0 ... 20 mA or 4 ... 20 mA
Power dissipation/power consumption ≤ 2 W / 2.2 W
Lead resistance max. 50 Ω
RTD Pt100, Pt500, Pt1000, Ni100, Ni1000
Thermocouples type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995)
Cold junction compensation external and internal
Collective error message Power Rail
Types of measuring 2-, 3-, 5-wire technology
Measurement loop monitoring sensor breakage
Sampling rate approx. 700 ms