| Параметр | Значение |
| Общие характеристики | |
| Артикул | 83580 |
| Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) Observe the temperature range limited by derating, see section derating. |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Degree of protection | IP20 |
| Connection | protected area: terminals 3, 4 unprotected area: terminals 1, 2 |
| Mass | approx. 20 g |
| Relative humidity | max. 95 % , without condensation |
| Mounting | pluggable in base module for mounting on 35 mm DIN mounting rail |
| Current | ≤ 8 mA |
| Marking | II 3G Ex ec IIC T4 Gc |
| Dimensions | 6.2 x 77 x 79 mm |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Designation | system components: - base module with screw terminals M-LB-5000 - base module with spring terminals M-LB-5000.SP - power feed module M-LB-5300 - fault status module M-LB-5400 - maintenance status module M-LB-5500 - universal power rail M-UPR-03-S - place holder module M-LB-5900 - separation wall M-UPR-I |
| Rated current | 500 mA , restrictions see derating characteristics |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Certificate | BVS 17 ATEX E 070 X |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 |
| Safety Integrity Level (SIL) | SIL 3 |
| Display elements | LED PWR (power supply), green LED LED FLT (fault signal), red LED LED CHK (maintenance signal), yellow LED |
| IECEx certificate | IECEx BVS 17.0061X |
| IECEx marking | Ex ec IIC T4 Gc |
| Nominal voltage | 1 V DC |
| Functional safety | IEC/EN 61508:2010 |
| Insertion loss | ≤ 0.04 dB, at 0 ... 4 kHz, in 600 Ω-System ≤ 3 dB, at 0 ... 450 kHz, in 100 Ω-System |
| Number of protected signal lines | 2 |
| Leakage current | < 5 µA at 1 V and 25 °C (77 °F) , line-line |
| Total discharge current (8/20 µs) | 20 kA (1x) |
| Maximum continuous operating voltage | 6 V DC |
| Nominal discharge current (8/20 µs) | 5 kA per line (10x) |
| Voltage protection level | max. 12 V line-line for nominal discharge current I max. 1400 V line-earth for nominal discharge current I |
| Topology | non-grounded |
| Series resistance | ≤ 0.6 Ω per line |
| Impulse rating | 1 kV/0.5 kA (category C1) 10 kV/5 kA (category C2) 1 kA (category D1) |
| Impulse discharge current (10/350 µs) | 1 kA per line (2x) |
| Impulse reset time | < 500 ms |
| Surge protective devices for low voltage | EN 61643-21:2001+A1:2009+A2:2013 IEC 61643-21:2001+A1:2008+A2:2012 |
| Rated surge current (8/20 µs) | 10 kA per line (1x) |
| Status indication | fault and maintenance signal via Universal Power Rail M-UPR-03-S |
| Signal lines/fault indication output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
| Signal lines/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |