Пт-Пн: 9:00 - 18:00

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Цены носят информационный характер и не являются публичной офертой. Точную цену и срок поставки подтвердит менеджер при оформлении заявки
Доставка в любой регион России транспортной
компанией на Ваш выбор
| Параметр | Значение |
| Общие характеристики | |
| Артикул | 82106 |
| Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Degree of protection | IP20 |
| Connection | terminals 3+, 4-; 3-, 4+ |
| Mass | approx. 20 g |
| Relative humidity | max. 95 % , without condensation |
| Mounting | pluggable in base module for mounting on 35 mm DIN mounting rail |
| Marking | II 3G Ex ec IIC T4 Gc |
| Dimensions | 6.2 x 77 x 79 mm |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Designation | system components: - base module with screw terminals M-LB-5000 - base module with spring terminals M-LB-5000.SP - protection module M-LB-XX-52XX - power feed module M-LB-5300 - fault status module M-LB-5400 - maintenance status module M-LB-5500 - universal power rail M-UPR-03-S - separation wall M-UPR-I |
| Contact loading | 30 V AC/0.5 A/cos φ 0.7; 30 V DC/0.5 A resistive load |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Certificate | BVS 17 ATEX E 070 X |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 |
| Display elements | LED PWR (power supply), green LED LED FLT (fault signal), yellow LED |
| Power dissipation | 0.25 W |
| Output rated operating current | 0.5 A |
| Output voltage | 30 V AC/DC |
| Energized/De-energized delay | < 1 s / < 1 s |
| IECEx certificate | IECEx BVS 17.0061X |
| IECEx marking | Ex ec IIC T4 Gc |
| Nominal voltage | see power feed module M-LB-5300 |
| Connection side | control side |
| Signal type | Digital Input |
| Output/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
| Status indication | fault signal via solid state relay (NO contact) to the control system |