| Параметр | Значение |
| Общие характеристики | |
| Артикул | 53767 |
| UL approval | E106378 |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Degree of protection | IP20 when mounted on backplane |
| Connection | removable front connector with spring terminal (0.14 ... 0.5 mm ) |
| Mass | approx. 90 g |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** |
| Power consumption | 1.55 W |
| Electromagnetic compatibility | NE 21 |
| Relative humidity | 95 % non-condensing |
| Current | 13 mA |
| Connection 2 | volt-free contact |
| Marking | II 3(1) G Ex nA [ia Ga] IIC T4 Gc I (M1) [Ex ia Ma] I II (1) D [Ex ia Da] IIIC |
| Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) |
| EU-type examination certificate | EXA 13 ATEX 0036X |
| IECEx approval | EXA 13.0003X |
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
| Approved for | Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I |
| System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure. |
| Power | 33 mW (linear characteristic) |
| LED indication | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-8) red: line fault (lead breakage or short circuit) , yellow: signal (per channel) |
| Directive 2014/30/EU | EN 61326-1 |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
| Directive 2014/34/EU | EN 60079-0:2011 EN 60079-11:2011 EN 60079-15:2010 |
| Power dissipation | 1.55 W |
| Voltage | 10 V |
| Line fault detection | can be switched on/off for each channel via configuration tool |
| Minimum pulse duration | 15 ms |
| ATEX approval | EXA 13 ATEX 0036X |
| Rated values | acc. to EN 60947-5-6 (NAMUR) |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA |
| Open-circuit | < 0.35 mA |
| Short-circuit | < 360 Ω |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Internal resistor | 1 kΩ |
| Interface | manufacturer-specific bus to standard com unit |
| Coding | optional mechanical coding via front socket |
| Occupied slots | 1 |
| Number of channels | 8 |
| Environmental test | EN 60068-2-14 |
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V |
| Lloyd Register | 15/20021 |
| Bureau Veritas Marine | 22449/B0 BV |