| Параметр | Значение |
| Общие характеристики | |
| Артикул | 59311 |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Degree of protection | IP20 when mounted on backplane |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm ) or screw terminals (0.08 ... 1.5 mm ) |
| Mass | approx. 90 g |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** |
| Power consumption | 0.4 W |
| Electromagnetic compatibility | NE 21 |
| Relative humidity | 95 % non-condensing |
| Measurement range | 10 ... 400 Ω (500 Ω incl. line resistance) |
| Linearity error | 0.1 % |
| Connection 2 | 3-wire sensor |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc |
| Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) |
| IECEx approval | BVS 09.0037X |
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
| Approved for | Ex nA [ic] IIC T4 Gc |
| System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure. |
| LED indication | Power LED (P) green: supply Status LED (1) red: line fault |
| Directive 2014/30/EU | EN 61326-1 |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
| Certificate | PF 08 CERT 1234 X |
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 |
| Power dissipation | 0.4 W |
| Connection 3 | 4-wire sensor |
| Measuring current | 200 µA |
| Line fault detection | can be switched on/off for each channel via configuration tool |
| Open-circuit | > 1 kΩ |
| Short-circuit | < 10 Ω |
| Influence of ambient temperature | max. 0,1 %/10 K |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Interface | manufacturer-specific bus to standard com unit |
| Coding | optional mechanical coding via front socket |
| Lead resistance | max. 50 Ω per strand |
| Occupied slots | 1 |
| Number of channels | 1 |
| Field device | resistance thermometer |
| Field device [3] | slide-wire sensors |
| Conversion time | max. 20 ms without LFD max. 150 ms with LFD |
| Environmental test | EN 60068-2-14 |
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V |
| Lloyd Register | 15/20021 |
| Bureau Veritas Marine | 22449/B0 BV |
| DNV GL Marine | TAA0000034 |
| Slide-wire sensor | 10 ... 400 Ω |
| Smallest span | 20 Ω for 0.1 % accuracy |