  • 1-channel
  • 1 digital output, 2 digital inputs
  • Inputs and output Ex ia
  • Installation in suitable enclosures in Zone 1
  • Module can be exchanged under voltage (hot swap)
  • Line fault detection switched on and off
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Permanently self-monitoring
  • Output with watchdog
  • Output with bus-independent safety shutdown input
Параметр Значение
Общие характеристики
Артикул 73524
Response time 10 ms (depending on bus cycle time)
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Degree of protection IP20 (module) , a separate housing is required acc. to the system description
Connection removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm ) or screw terminals (0.08 ... 1.5 mm )
Mass approx. 750 g
Rated voltage Use only in connection with the power supplies FB92**
Power consumption 1.85 W
Electromagnetic compatibility NE 21
Relative humidity 95 % non-condensing
Current 108 mA
Connection 2 volt-free contact
Marking II 2(1)G Ex db eb q [ia Ga] IIC Gb II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Vibration resistance frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Dimensions 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch)
EU-type examination certificate Presafe 19 ATEX 14054U
IECEx approval IECEx PRE 19.0009U
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Approved for Ex db eb q [ia Ga] IIC Gb [Ex ia Da] IIIC [Ex ia Ma] I
System information The module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate.
Power 654 mW
LED indication Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (O: output, I1: input 1, I2: input 2) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1)
Directive 2014/30/EU EN 61326-1
Shock resistance shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Directive 2014/34/EU EN 60079-0:2012+A11:2013 EN 60079-1:2014 EN 60079-5:2015 EN 60079-7:2015 EN 60079-11:2012
Power dissipation 1.3 W
Voltage 24.2 V
Current limit 50 mA
Line fault detection can be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms)
Open loop voltage 23 V
Minimum pulse duration 1 ms
ATEX approval Presafe 19 ATEX 14054U
Rated values acc. to EN 60947-5-6 (NAMUR)
Switching point/switching hysteresis 1.2 ... 2.1 mA / ± 0.2 mA
Open-circuit > 10 kΩ
Short-circuit < 50 Ω
Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Internal resistor 258 Ω
Interface manufacturer-specific bus to standard com unit
Coding optional mechanical coding via front socket
Internal capacitance 12 nF
Internal inductance 0 mH
Occupied slots 1
Number of channels 1
Field device Solenoid Valve
Field device [2] audible alarm
Field device [3] visual alarm
Environmental test EN 60068-2-14
Input/power supply, internal bus safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Watchdog within 0.5 s the device goes in safe state, e.g. after loss of communication
Output/power supply, internal bus safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V