| Параметр | Значение |
| Общие характеристики | |
| Артикул | 86046 |
| Response time | 20 ms (depending on bus cycle time) |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Degree of protection | IP20 (module) , a separate housing is required acc. to the system description |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm ) or screw terminals (0.08 ... 1.5 mm ) |
| Mass | approx. 350 g |
| Rated voltage | 12 V DC , only in connection with the power supplies FB92** |
| Power consumption | 1.7 W |
| Electromagnetic compatibility | NE 21 |
| Relative humidity | 95 % non-condensing |
| Current | 91.7 mA |
| Connection 2 | volt-free contact |
| Marking | II 2(1) G Ex d [ia Ga] IIC Gb |
| Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
| Dimensions | 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch) |
| EU-type examination certificate | PTB 97 ATEX 1074 U |
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 |
| System information | The module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate. |
| Power | 636 mW |
| LED indication | LED green: supply LED red: output line fault LED yellow: status output |
| Directive 2014/30/EU | EN 61326-1 |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 |
| Power dissipation | 1.4 W |
| Voltage | 27.83 V |
| Connection 3 | active binary signal 24 V DC |
| Current limit | 50 mA |
| Line fault detection | can be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms) |
| Open loop voltage | 24 V |
| Minimum pulse duration | 1 ms |
| ATEX approval | PTB 97 ATEX 1075 ; PTB 97 ATEX 1074 U |
| Rated values | acc. to EN 60947-5-6 (NAMUR) |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA |
| Open-circuit | > 2 kΩ |
| Short-circuit | < 145 Ω |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Internal resistor | 360 Ω |
| Interface | manufacturer-specific bus to standard com unit |
| Coding | optional mechanical coding via front socket |
| Internal capacitance | 1.65 nF |
| Occupied slots | 1 |
| Number of channels | 1 |
| Field device | Solenoid Valve |
| Field device [2] | audible alarm |
| Field device [3] | visual alarm |
| Environmental test | EN 60068-2-14 |
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V |
| Lloyd Register | 15/20021 |
| Bureau Veritas Marine | 22449/B0 BV |
| American Bureau of Shipping | T1450280/UN |
| DNV GL Marine | TAA0000034 |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V |