Параметр | Значение |
Общие характеристики | |
Артикул | 49762 |
Response time | 20 ms (depending on bus cycle time) |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description |
Connection | Ex e spring terminal with protective cover |
Mass | approx. 750 g |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** |
Power consumption | 2.35 W |
Electromagnetic compatibility | NE 21:2007 |
Relative humidity | 95 % non-condensing |
Marking | II 2 G Ex db eb IIC T4 |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) |
EU-type examination certificate | BVS 11 ATEX E 093 X |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
INMETRO | Brazil: TÜV 14.1599X |
System information | The module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate. |
LED indication | LED green: supply LED red: line fault , red flashing: communication error |
Directive 2014/30/EU | EN 61326-1:2006 |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-7:2007 |
Power dissipation | 2.35 W |
Current limit | 8 mA |
Line fault detection | can be switched on/off for each channel via configuration tool |
Open loop voltage | 20 V |
ATEX approval | BVS 11 ATEX E 093X |
Open-circuit | > 50 kΩ |
Short-circuit | < 300 Ω |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Interface | manufacturer-specific bus to standard com unit |
Coding | optional mechanical coding via front socket |
Occupied slots | 2 |
Number of channels | 8 |
Field device | Solenoid Valve |
Field device [2] | audible alarm |
Field device [3] | visual alarm |
Environmental test | EN 60068-2-14:2009 |
Bureau Veritas Marine | 22449/B0 BV |
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication |
Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V |
Test current | 0.33 mA |