Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

Digital Output with Shutdown Input FB6308B2

Digital Output with Shutdown Input FB6308B2
Digital Output with Shutdown Input FB6308B2

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 49762
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • 8-channel
  • Outputs with plug-in Ex e terminals
  • Installation in suitable enclosures in Zone 1
  • Module can be exchanged under voltage (hot swap)
  • Line fault detection (LFD)
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Permanently self-monitoring
  • Output with watchdog
  • Output with bus-independent safety shutdown input
  • Output with bus-independent safety shutdown
Параметр Значение
Общие характеристики
Артикул 49762
Response time 20 ms (depending on bus cycle time)
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Degree of protection IP20 (module) , a separate housing is required acc. to the system description
Connection Ex e spring terminal with protective cover
Mass approx. 750 g
Rated voltage 12 V DC , only in connection with the power supplies FB92**
Power consumption 2.35 W
Electromagnetic compatibility NE 21:2007
Relative humidity 95 % non-condensing
Marking II 2 G Ex db eb IIC T4
Vibration resistance frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Dimensions 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch)
EU-type examination certificate BVS 11 ATEX E 093 X
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
INMETRO Brazil: TÜV 14.1599X
System information The module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate.
LED indication LED green: supply LED red: line fault , red flashing: communication error
Directive 2014/30/EU EN 61326-1:2006
Shock resistance shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Directive 2014/34/EU EN 60079-0:2009 EN 60079-1:2007 EN 60079-7:2007
Power dissipation 2.35 W
Current limit 8 mA
Line fault detection can be switched on/off for each channel via configuration tool
Open loop voltage 20 V
ATEX approval BVS 11 ATEX E 093X
Open-circuit > 50 kΩ
Short-circuit < 300 Ω
Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Interface manufacturer-specific bus to standard com unit
Coding optional mechanical coding via front socket
Occupied slots 2
Number of channels 8
Field device Solenoid Valve
Field device [2] audible alarm
Field device [3] visual alarm
Environmental test EN 60068-2-14:2009
Bureau Veritas Marine 22449/B0 BV
Watchdog within 0.5 s the device goes in safe state, e.g. after loss of communication
Output/power supply, internal bus safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V
Test current 0.33 mA