Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

Float Switch LFL3-**-U

Float Switch LFL3-**-U
Float Switch LFL3-**-U

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 4135
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • Switch element: mercury (Hg)
  • Limit value detection for fluids
  • Sleeve design: small diameter, mounting through G1 tap hole possible
  • Ball design: high buoyancy
Параметр Значение
Общие характеристики
Артикул 4135
Материал float: PP (Polypropylene) cable: - PVC version: PVC cable, highly flexible (3 x 0.75 mm ) - PUR version: PUR cable, highly flexible (3 x 0.50 mm ) - CSM/CM version: CSM/CM cable (chlorinated polyethylene, (3 x 0.75 mm )) - TPK version: TPK cable, (3 x 0.75 mm )
Ambient temperature PVC version: 5 ... 70 °C (41 ... 158 °F) PUR version: 5 ... 70 °C (41 ... 158 °F) CSM/CM version: -20 ... 70 °C (-4 ... 158 °F) TPK version: 5 ... 70 °C (41 ... 158 °F)
Storage temperature -25 ... 70 °C (-13 ... 158 °F)
Degree of protection IP68
Switching point switch angle, measured against the horizontal: - upper switch point +15° ±5° - lower switch point -15° ±5°
Altitude ≤ 2000 m above MSL
Rated insulation voltage 300 V
Supplementary information Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Contact loading 230 V AC/3 A/200 VA; 150 V DC/3 A/100 W resistive load
Equipment architecture This device may be used with any sequential circuit, as long as the circuit can support the electrical circuit values of the switching elements.
Directive 2014/35/EU EN 60947-5-1:2004 + Cor.:2005 + A1:2009
Description mercury (Hg) change-over contact
Pulse withstand voltage 4 kV
Process pressure (static pressure) sleeve design: ≤ 3 bar at 20 °C (68 °F) ball design: ≤ 2 bar at 20 °C (68 °F)
Density sleeve design: ≥ 0.8 g/cm ball design: ≥ 0.6 g/cm
Installation instructions range of application and minimum length between mounting and float: - PVC version: ≥ 50 mm (2 inch), preferred for water - PUR version: ≥ 100 mm (4 inch), preferred for fuels, heating oils, oily fluids - CSM/CM version: ≥ 100 mm (4 inch), preferred for many acids and lyes - TPK version: ≥ 100 mm (4 inch), preferred for many acids and lyes mounting: - The float switch is mounted either from sidewards through a cable gland ≥ G1A into the vessel or - by means of a counter weight or rods (e. g. float switch combination) from the top. The pivot of the cable should always be horizontal.

Техподдержка

Опишитите свой вопрос, специалист службы технической поддержки свяжется с Вами в течении нескольких часов

Отправляя заявку, вы принимаете условия Политики конфиденциальности.

Спасибо!

Ваше сообщение успешно отправлено