Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

Fieldbus Segment Protector F2-SP-IC*

Fieldbus Segment Protector F2-SP-IC*
Fieldbus Segment Protector F2-SP-IC*

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 53244
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • 4 ... 10 outputs Ex ic (FISCO or Entity)
  • Advanced fault isolation at the spur
  • Segment Protector in Zone 2
  • Instruments in Zone 2 or Zone 1
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Advanced Diagnostics at the spur
  • Power, Com, Terminator, Diagnostics, and Error LEDs
Параметр Значение
Общие характеристики
Артикул 53244
Ambient temperature see table 2
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Degree of protection IP66
Housing see figure 1
Mass max 2.6 kg , depending on model
Rated voltage max. 31 V
Electromagnetic compatibility NE 21:2011
Relative humidity < 95 % non-condensing
Mounting panel mounting
Current 46 mA jumper 1, position 2 65 mA jumper 1, position 1
Marking II 3 G Ex nAc [ic] IIC T4 , II 2(3) D Ex tb [ic] IIIC T130°C (for cable gland version only)
Vibration resistance 5 g , 10 ... 150 Hz
Dimensions see table 2
Cable diameter see table 3
Connection type removable screw terminal , removable spring terminal , screw terminal
Housing material EN 1780-1 46000 , ISO AlSi9Cu3(Fe) , anodized
Core cross-section max. 2.5 mm /AWG 12-24
EU-type examination certificate TÜV 13 ATEX 107689 X
IECEx approval IECEx TUN 13.0004X
Supplementary information Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Approved for Ex nAc [ic] IIC T4 , Ex tb [ic] IIIC T130°C (for cable gland version only)
Rated current max. 32 mA jumper 1, position 2 max. 43 mA jumper 1, position 1
Directive 2014/30/EU EN 61326-1:2013
Shock resistance 15 g , 11 ms
Cable gland see table 2
Directive 2014/34/EU EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-31:2009
Design / Mounting Outside installation
Corrosion resistance acc. to ISA-S71.04-1985, severity level G3
Marine approval DNV A-14038
Terminating resistor selectable via Jumper 100 Ω +/- 10 %
Fieldbus standard IEC 61158-2
Short-circuit current 46 mA jumper 1, position 2 57 mA jumper 1, position 1
LED PWR green: Fieldbus voltage > 10 V and fieldbus terminator is deactivated
Voltage 32 V
Climatic conditions IEC 60721
Maximum safe voltage 35 V
Surge protection trunk, spurs overvoltage protected if voltage exceeds typ. 39 V, max. 41 V
Inductance 0.25 mH jumper 1, position 1 0.125 mH jumper 1, position 2
Capacitance 60 nF
Number of outputs see table "Technical data depending on model"
Number of devices per output 1
Self current consumption see table "Technical data depending on model"
Voltage drop main cable/outputs max. 1.2 V
Voltage drop trunk In/Out 0 V
LED COM/ERR yellow: flashing: fieldbus communication status and physical layer diagnostic status
LED SPURS red: 2 Hz flashing in short-circuit condition
LED PWR/TERM green: Fieldbus voltage > 10 V and fieldbus terminator is activated
Jumper 1 configuration of short-circuit current/rated current
Jumper 2 configuration of grounding option for trunk and cable screen/shield
FOUNDATION Fieldbus FF-846

Техподдержка

Опишитите свой вопрос, специалист службы технической поддержки свяжется с Вами в течении нескольких часов

Отправляя заявку, вы принимаете условия Политики конфиденциальности.

Спасибо!