Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 53244 |
Ambient temperature | see table 2 |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Degree of protection | IP66 |
Housing | see figure 1 |
Mass | max 2.6 kg , depending on model |
Rated voltage | max. 31 V |
Electromagnetic compatibility | NE 21:2011 |
Relative humidity | < 95 % non-condensing |
Mounting | panel mounting |
Current | 46 mA jumper 1, position 2 65 mA jumper 1, position 1 |
Marking | II 3 G Ex nAc [ic] IIC T4 , II 2(3) D Ex tb [ic] IIIC T130°C (for cable gland version only) |
Vibration resistance | 5 g , 10 ... 150 Hz |
Dimensions | see table 2 |
Cable diameter | see table 3 |
Connection type | removable screw terminal , removable spring terminal , screw terminal |
Housing material | EN 1780-1 46000 , ISO AlSi9Cu3(Fe) , anodized |
Core cross-section | max. 2.5 mm /AWG 12-24 |
EU-type examination certificate | TÜV 13 ATEX 107689 X |
IECEx approval | IECEx TUN 13.0004X |
Supplementary information | Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Approved for | Ex nAc [ic] IIC T4 , Ex tb [ic] IIIC T130°C (for cable gland version only) |
Rated current | max. 32 mA jumper 1, position 2 max. 43 mA jumper 1, position 1 |
Directive 2014/30/EU | EN 61326-1:2013 |
Shock resistance | 15 g , 11 ms |
Cable gland | see table 2 |
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-31:2009 |
Design / Mounting | Outside installation |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
Marine approval | DNV A-14038 |
Terminating resistor | selectable via Jumper 100 Ω +/- 10 % |
Fieldbus standard | IEC 61158-2 |
Short-circuit current | 46 mA jumper 1, position 2 57 mA jumper 1, position 1 |
LED PWR | green: Fieldbus voltage > 10 V and fieldbus terminator is deactivated |
Voltage | 32 V |
Climatic conditions | IEC 60721 |
Maximum safe voltage | 35 V |
Surge protection | trunk, spurs overvoltage protected if voltage exceeds typ. 39 V, max. 41 V |
Inductance | 0.25 mH jumper 1, position 1 0.125 mH jumper 1, position 2 |
Capacitance | 60 nF |
Number of outputs | see table "Technical data depending on model" |
Number of devices per output | 1 |
Self current consumption | see table "Technical data depending on model" |
Voltage drop main cable/outputs | max. 1.2 V |
Voltage drop trunk In/Out | 0 V |
LED COM/ERR | yellow: flashing: fieldbus communication status and physical layer diagnostic status |
LED SPURS | red: 2 Hz flashing in short-circuit condition |
LED PWR/TERM | green: Fieldbus voltage > 10 V and fieldbus terminator is activated |
Jumper 1 | configuration of short-circuit current/rated current |
Jumper 2 | configuration of grounding option for trunk and cable screen/shield |
FOUNDATION Fieldbus | FF-846 |