| Параметр | Значение |
| Общие характеристики | |
| Артикул | 53244 |
| Ambient temperature | see table 2 |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Degree of protection | IP66 |
| Housing | see figure 1 |
| Mass | max 2.6 kg , depending on model |
| Rated voltage | max. 31 V |
| Electromagnetic compatibility | NE 21:2011 |
| Relative humidity | < 95 % non-condensing |
| Mounting | panel mounting |
| Current | 46 mA jumper 1, position 2 65 mA jumper 1, position 1 |
| Marking | II 3 G Ex nAc [ic] IIC T4 , II 2(3) D Ex tb [ic] IIIC T130°C (for cable gland version only) |
| Vibration resistance | 5 g , 10 ... 150 Hz |
| Dimensions | see table 2 |
| Cable diameter | see table 3 |
| Connection type | removable screw terminal , removable spring terminal , screw terminal |
| Housing material | EN 1780-1 46000 , ISO AlSi9Cu3(Fe) , anodized |
| Core cross-section | max. 2.5 mm /AWG 12-24 |
| EU-type examination certificate | TÜV 13 ATEX 107689 X |
| IECEx approval | IECEx TUN 13.0004X |
| Supplementary information | Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
| Approved for | Ex nAc [ic] IIC T4 , Ex tb [ic] IIIC T130°C (for cable gland version only) |
| Rated current | max. 32 mA jumper 1, position 2 max. 43 mA jumper 1, position 1 |
| Directive 2014/30/EU | EN 61326-1:2013 |
| Shock resistance | 15 g , 11 ms |
| Cable gland | see table 2 |
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-31:2009 |
| Design / Mounting | Outside installation |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
| Marine approval | DNV A-14038 |
| Terminating resistor | selectable via Jumper 100 Ω +/- 10 % |
| Fieldbus standard | IEC 61158-2 |
| Short-circuit current | 46 mA jumper 1, position 2 57 mA jumper 1, position 1 |
| LED PWR | green: Fieldbus voltage > 10 V and fieldbus terminator is deactivated |
| Voltage | 32 V |
| Climatic conditions | IEC 60721 |
| Maximum safe voltage | 35 V |
| Surge protection | trunk, spurs overvoltage protected if voltage exceeds typ. 39 V, max. 41 V |
| Inductance | 0.25 mH jumper 1, position 1 0.125 mH jumper 1, position 2 |
| Capacitance | 60 nF |
| Number of outputs | see table "Technical data depending on model" |
| Number of devices per output | 1 |
| Self current consumption | see table "Technical data depending on model" |
| Voltage drop main cable/outputs | max. 1.2 V |
| Voltage drop trunk In/Out | 0 V |
| LED COM/ERR | yellow: flashing: fieldbus communication status and physical layer diagnostic status |
| LED SPURS | red: 2 Hz flashing in short-circuit condition |
| LED PWR/TERM | green: Fieldbus voltage > 10 V and fieldbus terminator is activated |
| Jumper 1 | configuration of short-circuit current/rated current |
| Jumper 2 | configuration of grounding option for trunk and cable screen/shield |
| FOUNDATION Fieldbus | FF-846 |