Параметр | Значение |
Общие характеристики | |
Артикул | 85850 |
Материал | Aluminum |
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Degree of protection | IP66 |
Connection | terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode |
Mass | approx. 1000 g |
Rated voltage | 7.2 V DC , battery operated |
Parameter assignment | - wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization |
Mounting | mounting on field device , panel or pole mounting |
Current | 4 ... 20 mA |
Transfer rate | 1200 Bit/s |
Marking | II 2G Ex ia IIC T4/T3 Gb II 2D Ex tb [ia] IIIC T70°C Db |
Protocol | HART 7.3, backward compatible |
Vibration resistance | 20 ... 2000 Hz, 0,01 g /Hz |
Dimensions | 92 x 89.5 x 92.8 mm (without cable glands and antenna) |
EU-type examination certificate | BVS 17 ATEX E 029 |
Designation | battery W-BAT-B2-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-F8MK threads (NPT 1/2", NPT 3/4", G 1/2, M20) |
Directive 2014/30/EU | EN 61326-1:2013, CLASS A |
Directive 2011/65/EU (RoHS) | EN 50581:2012 |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-31:2014 |
Supply | loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V |
Accuracy | current input: 0.125 % of measuring range |
Output rated operating current | 4 ... 20 mA |
Control drawing | 116-0435 |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 |
IECEx certificate | IECEX BVS 17.0023 |
Directive 2014/53/EU | EN 300328 V2.1.1:2017 , EN 301489-17 V3.1.1:2017 , EN 301489-1 V2.1.1:2017 |
Influence of ambient temperature | current input: 5 µA/K |
Suitable field devices | usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - up to four externally powered HART field devices operating in multidrop mode |
Number of devices | - one passive 4 ... 20 mA/HART field device - up to 4 HART field devices in multidrop mode |
Parameters | primary/secondary master, preambles, retries and short address scan ranges |
Output variables | PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 |