Параметр | Значение |
Общие характеристики | |
Артикул | 90288 |
Материал | Aluminum alloy with polyurethane enamel paint |
Ambient temperature | temperature class T5: -40 ... 85 °C (-40 ... 185 °F) temperature class T6: -40 ... 75 °C (-40 ... 167 °F) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Degree of protection | IP67 |
Connection | - 5 wires, 600 mm long, exiting from male thread NPT1/2 - 1 external grounding point |
Mass | 460 g |
Rated voltage | 7 ... 32 V DC |
Relative humidity | max. 100 % |
Marking | II 2 G Ex db IIC T6...T5 Gb II 2 D Ex tb IIIC T95°C Db |
Protocol | HART 7.1, backward compatible |
Dimensions | 60.8 x 60.8 x 100 mm (l x w x h) |
CSA approval | FM 17 NCA 0004 FM 17 CA 0102 X |
Standards | IEC 60079-0:2011 , IEC 60079-1:2014 , IEC 60079-31:2013 |
EU-type examination certificate | FM 17 ATEX 0046 X |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Approved for | XP Class I, II, III, Division 1, Groups A-G Ex db IIC T6...T5 Gb Ex tb IIIC T95°C Db |
Rated current | < 1 mA , max. 25 mA |
FM approval | FM 17 NUS 0010 FM 17 US 0191 X |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-1:2014 , EN 60079-31:2014 |
Supply | loop power for field devices voltage: 1 ... 2.5 V DC, adjustable in steps of 0.5 V |
Communication | WirelessHART specifications - physical layer: IEEE 802.15.4.2006 - frequency band: 2.4 GHz (ISM band, licence free) - maximum transmit power: +10 dBm - outdoor transmission range: 235 m - communication standard: WirelessHART |
Output rated operating current | 3.2 ... 25 mA |
Control drawing | 116-0425 (cFMus) |
IECEx certificate | IECEx FMG 17.0020X |
IECEx marking | Ex db IIC T6...T5 Gb , Ex tb IIIC T95°C Db |
Directive 2014/53/EU | EN 300 328 V2.1.1:2016 EN 301 489-1 V2.2.0:2017 EN 301 489-17 V3.2.0:2017 |
Interface | internal antenna |
Number of devices | up to 8 HART field devices (depending on installation) |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 , FCC ID: X89-WA1101 |