Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 27749 |
Control elements | DIP-switch |
Ripple | ≤ 10 % |
Switching frequency | ≤ 5 kHz |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 150 g |
Rated voltage | 20 ... 30 V DC |
Electromagnetic compatibility | NE 21:2004 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Current | 13 mA |
Marking | II 3G Ex nA II T4 |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Labeling | space for labeling at the front |
EU-type examination certificate | PTB 00 ATEX 2035 |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Power | 34 mW (linear characteristic) |
Rated current | ≤ 50 mA |
Output I | signal , electronic output, active |
Output II | signal or error message , electronic output, active |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Certificate | TÜV 99 ATEX 1499 X |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000 |
Safety Integrity Level (SIL) | SIL 2 |
Display elements | LEDs |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) |
Configuration | via DIP switches |
Control drawing | 116-0047 |
Galvanic isolation | IEC 62103:2003 |
IECEx certificate | IECEx PTB 05.0011 |
IECEx marking | [Ex ia] IIC , [Ex ia] I , [Ex ia] IIIC |
Voltage | 10.5 V |
Maximum safe voltage | 40 V DC (Attention! The rated voltage can be lower.) |
Signal level | 1-signal: (L+) - 3.5 V (100 mA, short-circuit protected) 0-signal: switched off (off-state current ≤ 10 µA) |
Connection side | control side |
Input | Ex ia IIC, Ex ia IIIC |
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Output/Output | not available , common pole terminal 14+ |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
Signal type | Digital Input |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Output/power supply | not available , common pole terminal 14+ |
Collective error message | Power Rail |