Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 48348 |
Control elements | Control panel |
UL approval | E223772 |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 300 g |
Rated voltage | 115 V AC ± 10 % |
Power consumption | 4 VA |
Input frequency | 0 ... 80 Hz , pulse divider 0 ... 1 kHz |
Electromagnetic compatibility | NE 21:2006 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Current | 13.5 mA |
Resolution | < 0.1 % of the set value, min. 10 ms |
Marking | II 3G Ex nA nC IIC T4 Gc |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 |
Mechanical life | 5 x 10 switching cycles |
Labeling | space for labeling at the front |
EU-type examination certificate | TÜV 99 ATEX 1408 |
IECEx approval | IECEx TUN 03.0000 |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Power | 34 mW (linear characteristic) |
Rated current | 35 mA |
Output I | terminals 10, 11, 12 non-intrinsically safe |
Contact loading | 50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load |
Output II | terminals 19+, 20- non-intrinsically safe |
Input I | terminals 1+, 3-: Ex ia |
Input II | terminals 13+, 14- non-intrinsically safe |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Certificate | TÜV 02 ATEX 1885 X |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
Display elements | LEDs , display |
Accuracy | 2 ms |
Energized/De-energized delay | after rising input flank 3 ms ; after falling input flank 2 ms |
Configuration | via operating buttons |
Control drawing | 116-0305 |
Directive 2014/35/EU | EN 61010-1:2010 |
Voltage | 10.1 V |
Maximum safe voltage | 40 V (Attention! The rated voltage can be lower.) |
Signal level | 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current ≤ 10 µA) |
Connection side | control side |
Line fault detection | breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA |
Signal type | Digital Input |
Open circuit voltage/short-circuit current | 12 V / 3.5 mA |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Pulse duration | min. 10 ms |
Influence of ambient temperature | 0.003 %/K (50 ppm) |
Active/Passive | I > 3 mA / I < 1.5 mA |
Input I/other circuits | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Output I, II against eachother | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
Output I/power supply and reset | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
Output II/reset | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V |
Output II/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
Reset/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |