SMART Universal Barrier HiC2441

SMART Universal Barrier HiC2441
SMART Universal Barrier HiC2441

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 93132
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • 1-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Analog input, digital input,
    analog output, digital output
  • No configuration required, device is self-adapting
  • HART transparency
  • Low power dissipation
  • 3-way isolation
  • Up to SIL 2 acc. to IEC 61508
Параметр Значение
Общие характеристики
Артикул 93132
Ripple 20 mV
Switching frequency ≤ 500 Hz with 50 % duty cycle (digital input, NAMUR sensor) ≤ 5 Hz (digital input, dry contact) ≤ 20 Hz (digital output)
UL approval E106378
Ambient temperature -40 ... 70 °C (-40 ... 158 °F) Observe the temperature range limited by derating, see section derating.
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Degree of protection IP20
Connection SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Mass approx. 100 g
Rated voltage 19 ... 30 V DC via Termination Board
Power consumption ≤ 700 mW
Deviation at 20 °C (68 °F) ≤ ±20 µA incl. linearity, hysteresis and supply fluctuations at 4 ... 20 mA (analog input, analog output) ≤ ±60 µA incl. linearity, hysteresis and supply fluctuations at 0 ... 45 mA (digital output)
Electromagnetic compatibility NE 21:2011
Relative humidity 95 % non-condensing
Mounting on Termination Board
Voltage drop approx. 4 V (current source)
Current 13 mA
Marking II 3G Ex ec IIC T4 Gc
Dimensions 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
EU-type examination certificate TÜV 14 ATEX 153522 X
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Power 41 mW
Signal 0.1 ... 9 mA
Rated current ≤ 30 mA
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Certificate TÜV 14 ATEX 153523 X
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015
Safety Integrity Level (SIL) SIL 2
Power dissipation 1.1 W at 24 V, 300 Ω load (digital output)
Control drawing 116-0408 (cULus)
IECEx certificate IECEx TUN 15.0004X
IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc
Voltage 12.6 V
Maximum safe voltage 250 V (Attention! The rated voltage can be lower.)
Reaction time ≤ 5 ms , turn-on/turn-off time (digital output)
Current limit 45 mA
Input EN 60947-5-6:2000
Load 0 ... 650 Ω
Line fault detection > 100 kΩ at max. 30 V, with field wiring open
Open loop voltage approx. 22 V
Signal type Universal
Frequency range HART: bandwidth by 0.5 V signal and/or 1 mA signal 950 ... 2500 Hz (analog input, analog output)
Influence of ambient temperature < 2 µA/K (0 ... 70 °C (32 ... 158 °F)) < 3 µA/K (-40 ... 0 °C (-40 ... 32 °F))
Input/Other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Protection against electrical shock IEC 61010-1:2010
Internal resistor min. 240 Ω
Coding pin 1 and 4 trimmed For further information see system description.
Drive capability 12 V / 40 mA at 300 Ω load
Suitable field devices solenoid valves, acoustic or visual alarms
Supply voltage min. 16 V at 20 mA (2-wire SMART transmitter)
Equipment SL2: 5a(+), 1a(-)
Settling time ≤ 20 ms (analog input, analog output) ≤ 1 ms (digital input, NAMUR sensor)
Control/power supply basic insulation according to IEC/EN 61010-1, rated insulation voltage 60 V