Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 42971 |
Control elements | DIP-switch |
Ripple | ≤ 10 % |
Switching frequency | ≤ 10 Hz |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection | IP20 |
Connection | SL1: 6b |
Mass | approx. 100 g |
Rated voltage | 19 ... 30 V DC bus powered via Termination Board |
Power consumption | ≤ 600 mW |
Electromagnetic compatibility | NE 21:2006 For further information see system description. |
Mounting | on Termination Board |
Current | 17.1 mA |
Marking | II 3G Ex nA nC IIC T4 Gc |
Output type | open collector transistor (internal fault bus) |
Dimensions | 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch) |
Mechanical life | 10 switching cycles |
Labeling | space for labeling at the front |
EU-type examination certificate | BASEEFA 06 ATEX 0093 X |
IECEx approval | IECEx BAS 06.0026X |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Power | 45 mW (linear characteristic) |
Rated current | ≤ 30 mA |
Output I | signal ; relay |
Contact loading | 50 V DC / 0.5 A |
Output II | signal ; relay |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Certificate | PF 08 CERT 1047 X |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
Safety Integrity Level (SIL) | SIL 2 |
Display elements | LEDs |
Power dissipation | ≤ 600 mW |
Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms |
Configuration | via DIP switches |
Control drawing | 116-0434 |
Galvanic isolation | EN 50178:1997 |
Voltage | 10.5 V |
Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) |
Connection side | control side |
Input | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Output/Output | basic insulation acc. to EN 50178, rated insulation voltage of 50 V AC |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA |
Signal type | Digital Input |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Minimum switch current | 2 mA / 24 V DC |
Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Output/power supply | basic insulation acc. to EN 50178, rated insulation voltage of 50 V AC |
Coding | pin 1 and 2 trimmed For further information see system description. |
Pulse/Pause ratio | min. 20 ms / min. 20 ms |