Параметр | Значение |
Общие характеристики | |
Артикул | 89584 |
Control elements | DIP-switch |
Switching frequency | - bus powered: filter OFF: max. 150 Hz, filter ON: max. 15 Hz - loop powered: max. 10 Hz |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection | IP20 |
Connection | SL1: 6b |
Mass | approx. 100 g |
Rated voltage | 20.4 ... 30 V DC loop powered 20.4 ... 30 V DC bus powered via Termination Board |
Electromagnetic compatibility | NE 21:2006 For further information see system description. |
Mounting | on Termination Board |
Current | 93 mA |
Marking | II 3G Ex ec IIC T4 Gc |
Output type | open collector transistor (internal fault bus) |
Dimensions | 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch) |
Labeling | space for labeling at the front |
EU-type examination certificate | CESI 10 ATEX 046 |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Power | 586 mW |
Inrush current | 0.2 A , 15 ms loop powered |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Certificate | KIWA 15 ATEX 0036 X |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015+A1:2018 |
Safety Integrity Level (SIL) | SIL 3 |
Display elements | LEDs |
Power dissipation | 1 W at 24 V, 300 Ω load for loop powered |
Energized/De-energized delay | - bus powered: filter OFF: 1 ms, filter ON: 10 ms - loop powered: switch-on 50 ms, switch-off 6 ms (300 Ω load) |
Configuration | via DIP switches |
Control drawing | 116-0383 (cULus) |
IECEx certificate | IECEx CES 10.0017 IECEx KIWA 15.0018X |
IECEx marking | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec IIC T4 Gc |
Voltage | 25.2 V |
Maximum safe voltage | 253 V AC (Attention! U is no rated voltage.) |
Control input | external switch (dry contact or open collector) non isolated or logic signal input fully floating |
Input current | 62 mA at 24 V, 300 Ω load |
Output | Ex ia Ga, Ex ia Da, Ex ia Ma |
Signal level | 1-signal: 15...30 V DC (current limited at 3 mA) or contact close (internal 10 kΩ pull-up) 0-signal: 0...5 V DC or contact open |
Connection side | field side |
Current limit | 55 mA |
Load | nominal 0.1 ... 5 kΩ |
Open loop voltage | approx. 22.5 V |
Signal type | Digital Output |
Internal resistor | approx. 280 Ω |
Coding | pin 2 and 3 trimmed For further information see system description. |
Fault current | 4 mA pulsing (20 ms ON, 200 ms OFF) |
Fault level | lead short-circuit detection at < 25 Ω lead breakage detection at > 100 kΩ typical |
Output/power supply, inputs, and collective error | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V |