Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 86242 |
Switching frequency | max. 10 Hz |
UL approval | E106378 |
Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) |
Degree of protection | IP20 |
Connection | SL2: 5a(+), 5b(-) |
Mass | approx. 150 g |
Rated voltage | 19 ... 30 V DC |
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 For further information see system description. |
Mounting | on Termination Board |
Current | 110 mA |
Marking | II 3(1)G Ex ec [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
Dimensions | 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch) |
Labeling | space for labeling at the front |
EU-type examination certificate | EXA 17 ATEX 0040 X |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Power | 715 mW |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card) |
Inrush current | ≤ 200 mA after 100 µs |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 |
Safety Integrity Level (SIL) | SIL 3 |
Display elements | LED |
Power dissipation | < 1.3 W |
Energized/De-energized delay | 28 ms / 10 ms |
Control drawing | 116-0447 (cULus) |
IECEx certificate | IECEx EXA 17.0009X |
IECEx marking | Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I |
Voltage | 26 V |
Maximum safe voltage | 60 V (Attention! The rated voltage can be lower.) |
Output | Ex ia |
Signal level | 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC |
Connection side | field side |
Current limit | 45 mA |
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 V |
Open loop voltage | typ. 24.6 V |
Signal type | Digital Output |
Protection against electrical shock | EN 61010-1:2010 |
Internal resistor | approx. 240 Ω |
Coding | pin 1 and 4 trimmed For further information see system description. |
Test pulse length | max. 2 ms from DO card |
Output/other circuits | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |