Параметр | Значение |
Общие характеристики | |
Артикул | 66955 |
MTTF | 100 a |
UL approval | An isolated source with a secondary open circuit voltage of ≤ 30 V with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed. UL mark does not provide UL certification for any functional safety rating or aspects of the device. |
Ambient temperature | 0 ... 55 °C (32 ... 131 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Degree of protection | IP20 |
Housing | Stainless steel |
Mass | 800 g |
Construction type | Low profile housing |
Interface type | Chip card slot |
Transfer rate | 10 MBit/s |
Protocol | Media Redundancy Protocol (MRP) |
B | 2.5 E+5 |
Response delay | < 40 ms |
Rated operating current | approx. 300 mA PELV |
Switch-on delay | < 10 s |
Noise immunity | EN 61000-6-4:2007/A1:2011 EN 61000-6-2/AC:2005 |
Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2/AC:2005, EN 61000-6-4:2007+A1:2011 |
Shock resistance | EN 61131-2:2004 |
Safety Integrity Level (SIL) | SIL 3 |
Physical | 2 x RJ-45 |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface; 24 V |
UL File Number | E223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source |
Number/Type | 6 inputs Safety: 3 x 2 channels Or 6 standard inputs |
Performance level (PL) | PL e |
Functional safety | EN ISO 13849-1:2008/AC:2009, EN ISO 13849-2:2012 (up to PL e), EN 61508:2010 and EN 62061:2005+A1:2013 (up to SIL3) |
Safety output | 6 semiconductor outputs Output circuits: 6 PNP transistor outputs Max. contact load: 1.2 A at 30 V , Σ = 7.2 A in total (see derating) |
Button | 4 |
AS-Interface specification | V3.0 |
PLC-Functionality | activateable |
Duplicate address detection | from AS-Interface slaves |
Earth fault detection | integrated |
EMC monitoring | integrated |
Diagnostics function | Extended function via display |
Display | Illuminated graphical LC display for addressing and error messages |
LED ETHERNET | PROFINET master detected; LED green |
LED AS-i ACTIVE | AS-Interface operation normal; LED green |
LED CONFIG ERR | configuration error; LED red |
LED PRG ENABLE | autom. programming; LED green |
LED POWER | voltage ON; LED green |
LED PRJ MODE | projecting mode active; LED yellow |
LED U AS-i | AS-Interface voltage; LED green |
LED AUX | ext. auxiliary voltage U ; LED green |
Insulation voltage | ≥ 500 V |
AS-Interface | EN 62026-2:2013 |
Switch SET | Selection and setting of a slave address |
OK button | Mode selection traditional-graphical/confirmation |
Button MODE | Mode selection PRJ-operation/save configuration/cursor |
ESC button | Mode selection traditional-graphical/cancel |
Data decoupling | integrated |
PROFINET | RJ-45 |
Directive 2006/42/EC | EN 61508:2010 EN ISO 13849-1/AC:2009 EN 62061:2005+A1:2013 |
LED IN | 6 x LED green |