Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

AS-Interface sensor module VBA-4E4E-G12-ZAJ

AS-Interface sensor module VBA-4E4E-G12-ZAJ
AS-Interface sensor module VBA-4E4E-G12-ZAJ

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 40397
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • A/B slave with extended addressing possibility for up to 62 slaves
  • One-piece housing with stainless steel base
  • Installation without tools
  • Metal threaded inserts with SPEEDCON technology
  • Flat cable connection with cable piercing technique, variable flat cable guide
  • Communication monitoring, configurable
  • Inputs for 2-, 3-, and 4-wire sensors
  • DIN rail mounting
  • AS-Interface certificate
  • Automatic addressing with latest masters in the event of replacement
Параметр Значение
Общие характеристики
Артикул 40397
MTTF 60 a
Mission Time (T 20 a
Diagnostic Coverage (DC) 0 %
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Degree of protection IP67
Connection cable piercing method flat cable yellow inputs: M12 round connector
Housing PBT
Mass 230 g
Switching point according to DIN EN 61131-2 (Type 2)
Relative humidity 85 % , noncondensing
Altitude ≤ 2000 m above MSL
Mounting Mounting plate
Protection class III
Pollution degree 3
Vibration resistance 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Shock and impact resistance 30 , 11 ms in 6 spatial directions 3 shocks 10 , 16 ms in 6 spatial directions 1000 shocks
Rated operating current ≤ 80 mA (without sensors) / max. 280 mA
Emitted interference EN 61000-6-4:2007
Noise immunity EN 61000-6-2:2005 EN 62026-2:2013
Directive 2014/30/EU EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Supply from AS-Interface
Fieldbus standard EN 62026-2:2013
Voltage 21 ... 31 V
Climatic conditions For indoor use only
Current loading capacity ≤ 200 mA, overload and short-circuit protected
Rated operating voltage 26.5 ... 31.6 V from AS-Interface
UL File Number E223772
Number/Type 2x 4 inputs for 2- or 3-wire sensors (PNP), DC alternative 2x 2 inputs for 4-wire sensors (PNP), DC
Surge protection U : Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral
Signal delay < 1 ms (input/AS-Interface)
Input current ≤ 8 mA (limited internally)
AS-Interface specification V3.0
AS-Interface EN 62026-2:2013
Slave type Double A/B slave
Required master specification ≥ V2.1
LED PWR/FAULT 2 Dual LEDs green/red green: AS-Interface voltage red: Communication error yellow/red flashing: Address 0 green/red flashing: Sensor supply overload
LED IN switching state (input); 8 LED yellow
0 (unattenuated) ≤ 2 mA
1 (attenuated) ≥ 6 mA
Input EN 61131-2
Profile S-0.A.2
IO code 0
ID code A
ID1 code Slave 1 Slave 2 1 2
ID2 code 2
D0 IN1.1 IN2.1
D1 IN1.2 IN2.2
D2 IN1.3 IN2.3
D3 IN1.4 IN2.4
P0 not used
P1 Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings)
P2 Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings)
P3 not used
Tightening torque, cable gland 0.4 Nm

Техподдержка

Опишитите свой вопрос, специалист службы технической поддержки свяжется с Вами в течении нескольких часов

Отправляя заявку, вы принимаете условия Политики конфиденциальности.

Спасибо!

Ваше сообщение успешно отправлено