Параметр | Значение |
Общие характеристики | |
Артикул | 3564 |
MTTF | 150 a at 30 °C |
Ambient temperature | 0 ... 70 °C (32 ... 158 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Degree of protection | IP65 |
Connection | cable piercing method or terminal compartment yellow flat cable or standard round cable inputs: M12 x 1.5 cable gland and cage tension spring terminals |
Housing | PA 6 GF30 |
Mass | 350 g |
Mounting | DIN mounting rail |
Protection class | III |
Resolution | 16 Bit / 0.1 °C |
Rated operating current | ≤ 80 mA |
Directive 2014/30/EU | EN 62026-2:2013 |
Supply | from AS-Interface |
LED PWR | AS-Interface voltage; LED green |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
UL File Number | E223772 |
Number/Type | 4 inputs for Pt100, 2- or 3-wire connection |
AS-Interface specification | V2.1 |
AS-Interface | EN 62026-2:2013 |
Slave type | Standard slave |
Required master specification | ≥ V2.1 |
Profile | S-7.3.E |
IO code | 7 |
ID code | 3 |
ID2 code | E |
P0 | mains power frequency filter P0=1, 50 Hz filter active P0=0, 60 Hz filter active |
P3 | configuration Pt100 P3=1, 2-wire connection P3=0, 3-wire connection |
LED FAULT | error display; LED red red: communication error red flashing: peripheral error |
LED ANALOG | status of input signal; LED green off: not connected (peripheral error) green: signal within measurement range green flashing: signal outside of measurement range (peripheral error) |
(function via AS-Interface) | The transfer of the data value is based on AS-Interface Profile 7.3. |
P1/P2 | Communication of the peripheral fault on measuring channels 1 to 4: [*PD-Z02313A*] |