  • 4 mm non-flush
Параметр Значение
Общие характеристики
Артикул 7366
MTTF 1750 a
Mission Time (T 20 a
Diagnostic Coverage (DC) 0 %
Switching frequency 0 ... 2000 Hz
CCC approval CCC approval / marking not required for products rated ≤36 V
Ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1.
Degree of protection IP67
Electromagnetic compatibility NE 21:2007
Output type 2-wire
Switching function Normally closed (NC)
Rated operating distance 4 mm
Installation non-flush
Assured operating distance 0 ... 3.24 mm
Switching state indicator LED, yellow
CSA approval cCSAus Listed, General Purpose
Connection type 4.8 mm Faston
Housing material PBT
Sensing face PBT
Hysteresis typ. 5 %
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions
CE marking [*PD-Z02585A*]
Control drawing 116-0451
Nominal voltage 8.2 V (R approx. 1 kΩ)
NAMUR EN 60947-5-6:2000 IEC 60947-5-6:1999
ATEX marking II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
Appropriate type NCN4-V3-N0...
Effective internal capacitance max. 100 nF ; a cable length of 10 m is considered.
Effective internal inductance max. 100 µH ; a cable length of 10 m is considered.
Use in the hazardous area see instruction manuals
Category 1G; 2G; 1D
Measuring plate not detected ≥ 3 mA
Measuring plate detected ≤ 1 mA
Maximum permissible ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Reduction factor r 0.7
Ordinary Location E87056
Hazardous Location E501628