| Параметр | Значение |
| Общие характеристики | |
| Артикул | 59323 |
| Switching voltage | 30 V DC / AC |
| Switching current | 1 A DC / AC resistive load |
| Response time | 20 ms (depending on bus cycle time) |
| UL approval | E106378 |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Degree of protection | IP20 when mounted on backplane |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm ) or screw terminals (0.08 ... 1.5 mm ) |
| Mass | approx. 160 g |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** |
| Power consumption | 1.4 W |
| Electromagnetic compatibility | NE 21 |
| Relative humidity | 95 % non-condensing |
| Marking | II 3 G Ex nA nC IIC T4 Gc |
| Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
| Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) |
| IECEx approval | BVS 09.0037X |
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
| Approved for | Ex nA nC IIC T4 Gc |
| System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure. |
| LED indication | Power LED (P) green: supply Status LED (I) red: communication error |
| Directive 2014/30/EU | EN 61326-1 |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
| Certificate | PF 08 CERT 1234 X |
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 |
| Power dissipation | 1.4 W |
| Electrical life | 0.1 mio. cycles |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Switch power | 30 VA / 30 W |
| Interface | manufacturer-specific bus to standard com unit |
| Coding | optional mechanical coding via front socket |
| Occupied slots | 2 |
| Number of channels | 8 |
| Environmental test | EN 60068-2-14 |
| Lloyd Register | 15/20021 |
| Bureau Veritas Marine | 22449/B0 BV |
| DNV GL Marine | TAA0000034 |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 61010-1 |
| Minimum load | 1 V 1 mA |
| Contact Material | AgPd gold plated |