Bus Coupler ISCM8100

Bus Coupler ISCM8100
Bus Coupler ISCM8100

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 43358
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • Com unit for 80 analog or 184 digital channels
  • HART communication via the bus
  • Device installation in Zone 2 or Zone 22
  • Configuration via I/A system user interface
  • Nonvolatile memory for configuration and parameter settings
  • Self configuration in redundant systems
  • Outputs drive to safe state in case of failures
  • Supports single and multichannel I/O modules
  • ON/OFF delay for digital inputs (filter, pulse extension)
  • Quick communication set-up
Параметр Значение
Общие характеристики
Артикул 43358
UL approval QUZW7.E106378
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Degree of protection IP20 (module) , mounted on backplane
Connection device plug (accessories) front connector for letterbug and service bus
Mass 150 g
Rated voltage 5 V DC , only in connection with the power supplies FB92**
Power consumption 2 W
Electromagnetic compatibility NE 21
Relative humidity 95 % non-condensing
Marking II 3 G Ex nA IIC T4
Vibration resistance frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Dimensions 32 x 100 x 103 mm (1.26 x 3.9 x 4 inch)
Labeling space for labeling at the front
IECEx approval BVS 08.0011X
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
System information The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure.
LED indication LED green: supply LED red: fault LED yellow: communication status
Directive 2014/30/EU EN 61326-1
Shock resistance shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Certificate PF 08 CERT 1234
Directive 2014/34/EU EN 60079-0 , EN 60079-1 , EN 60079-11
Supply only in connection with the power supplies LB9***
Fieldbus standard HDLC via terminals on backplane
Damaging gas for plugs: 21 days in 25 ppm SO , at 25 °C and 75 % rel. humidity, device G3
Environmental test HDLC to ISO 13239
Bus length max. 150 m (500 feet)
Station connection directly to PCS