Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

HART Transmitter Power Supply LB3106A 59236

HART Transmitter Power Supply LB3106A

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 59236
Под заказ
Запрос цены

Цены носят информационный характер и не являются публичной офертой. Точную цену и срок поставки подтвердит менеджер при оформлении заявки

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • 4-channel
  • Inputs Ex ia
  • Mounting in Zone 2, Class I/Div.2 or in the safe area
  • Power supply for 2-wire transmitters with 4 mA ... 20 mA
  • Supply circuit 15 V (20 mA)
  • HART communication via field bus or service bus
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD): one LED per channel
  • Permanently self-monitoring
  • Module can be exchanged under voltage
Параметр Значение
Общие характеристики
Артикул 59236
UL approval E106378
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Degree of protection IP20 when mounted on backplane
Connection removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm ) or screw terminals (0.08 ... 1.5 mm )
Mass approx. 90 g
Rated voltage 12 V DC , only in connection with the power supplies LB9***
Power consumption 2.7 W
Electromagnetic compatibility NE 21:2007
Relative humidity 95 % non-condensing
Current 87 mA
Resolution 12 Bit (0 ... 26 mA)
Marking II 3(1) G Ex nA [ia Ga] IIC T4 Gc I (M1) [Ex ia Ma] I II (1) D [Ex ia Da] IIIC
Vibration resistance frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Dimensions 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
EU-type examination certificate BVS 11 ATEX E 116 X
IECEx approval BVS 11.0068X
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Approved for Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I
System information The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Power 575 mW (linear characteristic)
LED indication Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit)
Directive 2014/30/EU EN 61326-1:2006
Shock resistance shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Directive 2014/34/EU EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 60079-26:2007 EN 61241-11:2006
Power dissipation 1.5 W
Voltage 27 V
Input resistance 15 Ω
Line fault detection can be switched on/off for each channel via configuration tool , configurable via configuration tool
ATEX approval BVS 11 ATEX E 116X
Open-circuit factory setting: < 1 mA configurable between 0 ... 26 mA
Short-circuit factory setting: > 22 mA configurable between 0 ... 26 mA
Influence of ambient temperature 0.1 %/10 K of the signal range
Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Interface manufacturer-specific bus to standard com unit
Coding optional mechanical coding via front socket
Occupied slots 1
Number of channels 4
Field device pressure converter
Field device [2] flow converter
Field device [3] level converter
Field device [4] Temperature Converter
Transmitter supply voltage min. 15 V at 20 mA ; 21.5 V at 4 mA
Conversion time max. 100 ms
HART communication yes
HART secondary variable no
After calibration 0.1 % of the signal range at 20 °C (68 °F)
Refresh time 100 ms
Environmental test EN 60068-2-14:2009
Input/power supply, internal bus safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Lloyd Register 15/20021
Bureau Veritas Marine 22449/B0 BV

Техподдержка

Опишитите свой вопрос, специалист службы технической поддержки свяжется с Вами в течении нескольких часов

Отправляя заявку, вы принимаете условия Пользовательского соглашения.

Спасибо!

Ваше сообщение успешно отправлено