Параметр | Значение |
Общие характеристики | |
Артикул | 49711 |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description |
Connection | Ex e spring terminal with protective cover |
Mass | approx. 350 g |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** |
Power consumption | 0.75 W |
Electromagnetic compatibility | NE 21:2007 |
Relative humidity | 95 % non-condensing |
Connection 2 | volt-free contact |
Marking | II 2 G Ex db eb IIC T4 |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
Dimensions | 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch) |
EU-type examination certificate | BVS 11 ATEX E 093 X |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
EAC approval | Russia: RU C-IT.MIII06.B.00129 |
INMETRO | Brazil: TÜV 14.1599X |
System information | The module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate. |
LED indication | LED green: supply LED red: line fault, per channel LED yellow: signal (status), per channel |
Directive 2014/30/EU | EN 61326-1:2006 |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-7:2007 |
Power dissipation | 0.75 W |
Connection 3 | active binary signal 24 V DC |
Line fault detection | can be switched on/off for each channel via configuration tool |
Minimum pulse duration | 20 ms |
ATEX approval | BVS 11 ATEX E 093X |
Rated values | acc. to EN 60947-5-6 (NAMUR) |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA |
Open-circuit | < 0.35 mA |
Short-circuit | < 360 Ω |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Internal resistor | 1 kΩ |
Interface | manufacturer-specific bus to standard com unit |
Coding | optional mechanical coding via front socket |
Occupied slots | 1 |
Number of channels | 3 |
Environmental test | EN 60068-2-14:2009 |
Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V |
Lloyd Register | 15/20021 |
Bureau Veritas Marine | 22449/B0 BV |
American Bureau of Shipping | T1450280/UN |