Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

Relay output FB6305B200

Relay output FB6305B200
Relay output FB6305B200

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 73870
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • 4-channel
  • Outputs wired to Ex e terminals
  • Installation in suitable enclosures in Zone 1
  • Module can be exchanged under voltage (hot swap)
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Permanently self-monitoring
  • Output with watchdog
Параметр Значение
Общие характеристики
Артикул 73870
Switching voltage DC: 30 V AC: 230 V
Switching current 1 A DC / AC resistive load
Response time 20 ms (depending on bus cycle time)
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Degree of protection IP20 (module) , a separate housing is required acc. to the system description
Connection wire ends or shielded cable tail wiring connection: separately covered Ex e terminals required
Mass approx. 750 g
Rated voltage 12 V DC , only in connection with the power supplies FB92**
Power consumption 1.05 W
Electromagnetic compatibility NE 21
Relative humidity 95 % non-condensing
Marking II 2 G Ex d IIC Gb
Vibration resistance frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Dimensions 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch)
EU-type examination certificate PTB 97 ATEX 1074 U
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
System information The module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate.
LED indication LED green: supply LED red: communication fault
Directive 2014/30/EU EN 61326-1
Shock resistance shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Directive 2014/34/EU EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006
Power dissipation 1.05 W
Electrical life 0.1 mio. cycles
Directive 2006/95/EC EN 61010-1
Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Switch power 30 W , AC: 250 VA
Interface manufacturer-specific bus to standard com unit
Occupied slots 2
Number of channels 4
Environmental test EN 60068-2-14
Bureau Veritas Marine 22449/B0 BV
Watchdog within 0.5 s the device goes in safe state, e.g. after loss of communication
Output/power supply, internal bus safe electrical isolation acc. to EN 61010-1
Minimum load 1 V 1 A
Contact Material AgPd gold plated

Техподдержка

Опишитите свой вопрос, специалист службы технической поддержки свяжется с Вами в течении нескольких часов

Отправляя заявку, вы принимаете условия Политики конфиденциальности.

Спасибо!

Ваше сообщение успешно отправлено