Пт-Пн: 9:00 - 18:00

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Цены носят информационный характер и не являются публичной офертой. Точную цену и срок поставки подтвердит менеджер при оформлении заявки
Доставка в любой регион России транспортной
компанией на Ваш выбор
| Параметр | Значение |
| Общие характеристики | |
| Артикул | 51303 |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Degree of protection | IP20 (module) , a separate housing is required acc. to the system description |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm ) or screw terminals (0.08 ... 1.5 mm ) |
| Mass | approx. 750 g |
| Rated voltage | 12 V DC , only in connection with the power supplies FB92** |
| Power consumption | 3.3 W |
| Electromagnetic compatibility | NE 21:2007 |
| Relative humidity | 95 % non-condensing |
| Current | 87 mA |
| Marking | II 2(1) G Ex d [ia Ga] IIC T4 Gb II (1) D [Ex ia Da] IIIC |
| Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
| Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) |
| EU-type examination certificate | BVS 12 ATEX E 015 X |
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 |
| INMETRO | Brazil: TÜV 14.1595X |
| System information | The module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate. |
| Power | 575 mW (linear characteristic) |
| LED indication | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) |
| Directive 2014/30/EU | EN 61326-1:2006 |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 |
| Power dissipation | 2.15 W |
| Voltage | 27 V |
| Load | 750 Ω max. |
| Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool |
| ATEX approval | BVS 12 ATEX E 015 X |
| Open-circuit | deviation of preset output value > 0.5 mA |
| Short-circuit | factory setting: < 50 Ω configurable between 0 ... 26 mA |
| Influence of ambient temperature | 0.1 %/10 K of the signal range |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Interface | manufacturer-specific bus to standard com unit |
| Coding | optional mechanical coding via front socket |
| Occupied slots | 2 |
| Number of channels | 4 |
| Field device | Proportional Valve |
| Field device [2] | I/P converters |
| Field device [3] | on-site display |
| HART communication | no |
| HART secondary variable | no |
| After calibration | 0.1 % of the signal range at 20 °C (68 °F) |
| Refresh time | 100 ms |
| Environmental test | EN 60068-2-14:2009 |
| Lloyd Register | 15/20021 |
| Bureau Veritas Marine | 22449/B0 BV |
| American Bureau of Shipping | T1450280/UN |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V |