Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 51857 |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection | IP20 |
Connection | 26-pin flat cable for analog connections 14-pin flat cable for master-slave connection between KFD2-HMM-16 and KFD0-HMS-16 |
Mass | approx. 100 g |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Marking | II 3G Ex nA IIC T4 Gc |
Dimensions | 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) , housing type B1 |
Labeling | space for labeling at the front |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Certificate | PF 07 CERT 1143 X |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
Safety Integrity Level (SIL) | SIL 3 |
Output voltage | ≥ 400 mV (with the terminator resistance specified above) |
Terminating resistor | external 230 ... 500 Ω standard (up to 1000 Ω possible) |
Input impedance | according to HART specification |
Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) |
Input voltage range | 0.08 ... 4 V ; typ. ± 5.2 V as local reference |
Output resistance | 100 Ω or smaller, capacitive coupling |
Conformity | HART field device input (revision 5 to 7) |