Параметр | Значение |
Общие характеристики | |
Артикул | 42264 |
Control elements | DIP switches at the housing side for: - unit slave address - baud rate - test mode on/off |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection | IP20 |
Connection | SL1: 1a, 1b(-); 2a, 2b(+) |
Mass | approx. 140 g |
Rated voltage | 20.4 ... 30 V DC via Termination Board |
Type | RS-485 , differential pair and grounding |
Electromagnetic compatibility | NE 21:2012 For further information see system description. |
Relative humidity | 5 ... 95 %, noncondensing |
Mounting | on Termination Board |
Transfer rate | 9600 MBit/s, 19200 MBit/s or 38400 MBit/s, selectable via switch |
Marking | II 3G Ex ec IIC T4 Gc |
Dimensions | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
Labeling | space for labeling at the front |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Impedance | high impedance |
Approved for | Class I, Division 2, Groups A, B, C, D and non-explosion hazardous area |
Rated current | 28 mA at 24 V , RS-485, quiescent current |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Certificate | CML 17 ATEX 3337 X |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 |
Safety Integrity Level (SIL) | SIL 3 |
Display elements | LEDs LED PWR ON (power supply), one green LED LED HART TX (HART transmission), one yellow LED LED FAULT (lead fault), one red LED |
Power dissipation | 0.7 W at 24 V |
Output voltage | ≥ 400 mV (with the terminator resistance specified above) |
Configuration | via DIP switches |
IECEx certificate | IECEx CML 17.0178X |
IECEx marking | Ex ec IIC T4 Gc |
Terminating resistor | external 230 ... 500 Ω standard (up to 1000 Ω possible) |
Input impedance | > 5 kΩ , according to HART specification |
Device type | DC isolated bus device |
Interface/power supply | 500 V |
Number of channels | 32 |
Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) |
Input voltage range | 0.12 ... 1.5 V |
Topology | multi point, master/slave connection |
CSA certificate | 1256050 |
Output resistance | 100 Ω or smaller, capacitive coupling |
Common mode voltage | max. 30 V |
Signal range | 0.12 V < signal < 1.5 V |
Address | 1 ... 31 , adjustable via DIP switch |
Conformity | HART field device input (revision 5 to 7) |
DC isolation | dual capacitor each channel |
Differential mode clamping | ± 5.2 V , for transient or AC signals |
Common mode clamping | ± 10 V , for transient or AC signals |
Carrier detect level | signal > 0.12 V , carrier detection activated signal < 0.08 V , carrier detection not activated |
Transmit amplitude | 200 Ω load, 0.43 V < signal < 0.49 V 500 Ω load, 1.1 V < signal < 1.2 V |
Data link type | HART primary and secondary |
Field multi point support | option available upon request |
Interface/field channels | 1000 V |
Power supply/field channels | 1000 V |