Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

WirelessHART Temperature Converter WHA-UT-F7B1-0-PP-Z1-Ex2

WirelessHART Temperature Converter WHA-UT-F7B1-0-PP-Z1-Ex2
WirelessHART Temperature Converter WHA-UT-F7B1-0-PP-Z1-Ex2

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 41126
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • 2-channel
  • Installation in Zone 1
  • WirelessHART converter
  • Battery operated
  • Thermocouple or RTD input
  • Output WirelessHART wireless interface
  • Internal antenna
Параметр Значение
Общие характеристики
Артикул 41126
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -20 ... 70 °C (-4 ... 158 °F)
Degree of protection IP65
Connection 2-wire: 2 sensors, 3- or 4-wire: 1 sensor
Mass approx. 1000 g
Rated voltage 3.6 V DC , battery operated
Parameter assignment - sampling period: 1, 2, 5, 10, 30 seconds or 1, 2, 5, 10, 30, 60 minutes - transmit power: configurable 0 dBm or 10 dBm (EIRP) - sensor type - mapping of input measuring values 1 and 2 into primary variable (PV) and secondary variable (SV) - publishing of up to three messages from the device, transmission rate selectable from 4 seconds to 60 minutes
Mounting panel or pole mounting
Measurement range -100 ... 100 mV , 0 ... 300 mV
Dimensions 77 x 129 x 177 mm (3 x 5.08 x 6.97 inch)
IECEx approval IECEx INE 09.0025X
Designation battery W-BAT-B1-Li mandatory for use in connection with hazardous areas (order separately) Mounting set W-ACC-F7MK External cold junction compensation W-ACC-CJC
EC-Type Examination Certificate IMQ 09 ATEX 008X
Approved for Ex ia IIC T4
Group, category, type of protection II 2(1)G Ex ia [ia] IIC T4
Directive 94/9/EC EN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007
FM approval CoC 3042534
Accuracy IEC 61298-3
Corrosion resistance acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60
Directive 2004/108/EC EN 61326-1:2006
Voltage mV Input
Input resistance ≥ 1 MΩ
Power dissipation/power consumption < 0.09 W
Lead resistance max. 10 Ω
Output variables PV: input 1 (°C, Ω, mV) SV: input 2 (°C, Ω, mV) TV: CJC temperature (°C) estimated battery life (days) battery voltage (volts) residual battery capacity (%)
Radio and telecommunication terminal equipment The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning.
FCC CFR47 Part 15 B and C ANSI C63.4-2003
RTD type Pt100, Pt1000 (IEC 751: 1995; GOST: alpha = 0.391)
Measuring circuit monitoring sensor breakage
Thermocouples type E, J, K, T (IEC 584-1)
Cold junction compensation internal , external
Directive 99/5/EC ETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001

Техподдержка

Опишитите свой вопрос, специалист службы технической поддержки свяжется с Вами в течении нескольких часов

Отправляя заявку, вы принимаете условия Политики конфиденциальности.

Спасибо!