Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

Switch Amplifier HiD2824

Switch Amplifier HiD2824
Switch Amplifier HiD2824

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 23312
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • 4-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Dry contact or NAMUR inputs
  • 4 relay contact outputs
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC 61508
Параметр Значение
Общие характеристики
Артикул 23312
Control elements DIP-switch
Switching frequency < 10 Hz
Response time 20 ms
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Degree of protection IP20
Connection SL1: 6b
Mass approx. 140 g
Rated voltage 20.4 ... 30 V DC bus powered via Termination Board
Switching point contact open 0.2 ... 1.2 mA, contact closed 2.1 ... 6.5 mA
Connectable sensor types potential free contact or proximity sensor
Electromagnetic compatibility NE 21:2006 For further information see system description.
Relative humidity 5 ... 90 %, non-condensing up to 35 °C (95 °F)
Mounting on Termination Board
Current 20 mA
Marking II 3G Ex nA nC IIC T4 Gc
Output type open collector transistor (internal fault bus)
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Mechanical life 10 switching cycles
Labeling space for labeling at the front
EU-type examination certificate CESI 02 ATEX 086
IECEx approval IECEx TUN 04.0012
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Approved for [Ex ia] IIC
Power 66 mW
Rated current 15 mA at 24 V, relay energized (per channel)
Contact loading 50 V DC / 0.5 A non-inductive
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Certificate PF 11 CERT 2109 X
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
Safety Integrity Level (SIL) SIL 2
Display elements LEDs
Power dissipation 0.35 W at 24 V (per channel)
Configuration via DIP switches
Control drawing 366-005CS-12B (cCSAus)
Galvanic isolation EN 50178:1997
Voltage 13.2 V
Maximum safe voltage 250 V AC (Attention! U is no rated voltage.)
Output signal: relay SPST per channel, phase selectable
Connection side control side
Input Ex ia, Ex iaD
Input/Output safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Output/Output functional insulation acc. to DIN EN 50178, rated insulation voltage 50 V
Line fault detection breakage 0 ... 0.2 mA, short-circuit 6.5 mA ... maximum value
Signal type Digital Input
Rated values acc. to EN 60947-5-6 (NAMUR)
Input/power supply safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Output/power supply functional insulation acc. to DIN EN 50178, rated insulation voltage 50 V
Coding pin 1 and 2 trimmed For further information see system description.
Input/input safe electrical isolation acc. to EN 60079-11:2007, voltage peak value 60 V