Параметр | Значение |
Общие характеристики | |
Артикул | 66116 |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Degree of protection | IP20 For safety applications: Installation in an enclosure with a minimum protection class of IP54 required |
Connection | Removable push-in terminals rated connection capacity: rigid: 0.20 mm ... 1.5 mm flexible (without wire end ferrule): 0.20 mm ... 2.5 mm flexible (with wire end ferrule): 0.25 mm ... 1.5 mm |
Housing | PA 66-FR |
Mass | 110 g |
Switching point | according to DIN EN 61131-2 (type 1) |
Relative humidity | 85 % , noncondensing |
Altitude | ≤ 2000 m above MSL |
Mounting | DIN mounting rail |
Protection class | III |
Current | 2 A Per output, total 4 A (T ≤ 60 °C) 1 A Per output, total 4 A (T ≤ 70 °C) |
Usage category | DC-13 |
Pollution degree | 2 |
Vibration resistance | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
Rated insulation voltage | 92 V |
Shock and impact resistance | 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks |
Rated operating current | ≤ 35 mA (without sensors) / max. 190 mA |
Emitted interference | EN 61000-6-4:2007 |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026:2013 |
Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
Supply | from external auxiliary voltage U |
Fieldbus standard | EN 62026-2:2013 |
LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
Voltage | ≥ (U - 0.5 V) |
Climatic conditions | For indoor use only |
Current loading capacity | ≤ 150 mA, overload- and short-circuit protected (INT) |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
UL File Number | E223772 |
Number/Type | 4 electronic outputs, PNP, overload and short-circuit proof |
Functional safety | EN ISO 13849-1:2008 EN ISO 13849-2:2012 |
Surge protection | U , U , U : overvoltage category II, safe isolated power supplies (PELV) Overvoltage category of the power supplies (primary): III |
Signal delay | < 1 ms (input/AS-Interface) |
Input current | ≤ 5.6 mA (max.) |
Electrical safety | IEC 61140:2009 |
AS-Interface specification | V3.0 |
LED AUX | ext. auxiliary voltage U ; dual LED green/red green: voltage OK red: reverse voltage |
AS-Interface | EN 62026-2:2013 |
MTBF | 141 a |
Directive 2006/42/EC | EN ISO 13849-1:2008 , EN ISO 13849-2:2012 |
Slave type | Standard slave |
Required master specification | ≥ V2.0 |
LED IN | switching state (input); 4 LED yellow |
0 (unattenuated) | ≤ 0.5 mA |
1 (attenuated) | ≥ 2 mA |
Input | EN 61131-2:2004 |
Profile | S-7.0 |
IO code | 7 |
ID code | 0 |
ID1 code | F |
ID2 code | E |
D0 | IN1 O1 |
D1 | IN2 O2 |
D2 | IN3 O3 |
D3 | IN4 O4 |
P0 | Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings) |
P1 | Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings) |
P2 | Lead breakage outputs P2 = 0 lead breakage on P2 = 1 lead breakage off (default settings) |
P3 | not used |
LED FAULT | Error display; red LED red: communication error, i.e. address is 0 red flashing: overload internal input supply, i.e. overload or lead interruption outputs |
Auxiliary voltage (output) | 20 ... 30 V DC PELV |
LED OUT | switching state (output); 4 LED yellow/red yellow: output active red: output overload or lead interruption |
LED INT | Internal input supply active; LED green |
Auxiliary voltage (input) | 12 ... 30 V DC PELV |
Pulse withstand voltage | 0.8 kV |