Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 43819 |
MTTF | 120 a |
Mission Time (T | 20 a |
Diagnostic Coverage (DC) | 0 % |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Degree of protection | IP68 / IP69K |
Connection | AS-Interface/U : AS-Interface flat cable Inputs/outputs: M12 round connector |
Housing | PBT PC |
Mass | 200 g |
Switching point | according to DIN EN 61131-2 (Type 2) |
Relative humidity | 85 % , noncondensing |
Altitude | ≤ 2000 m above MSL |
Mounting | Mounting plate |
Protection class | III |
Current | 2 A per output TB ≤ 40 °C: 6 A total TB ≤ 70 °C: sum O1 + O2 max. 2 A, sum O3 + O4 max. 2 A |
Pollution degree | 3 |
Vibration resistance | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
Shock and impact resistance | 30 , 11 ms in 6 spatial directions 3 shocks 10 , 16 ms in 6 spatial directions 1000 shocks |
Rated operating current | ≤ 40 mA (without sensors) / max. 240 mA |
Emitted interference | EN 61000-6-4:2007 |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 |
Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
Supply | from external auxiliary voltage U |
Fieldbus standard | EN 62026-2:2013 |
Voltage | ≥ (U - 0.5 V) |
Climatic conditions | For indoor use only |
Mounting screw | Stainless steel 1.4305 / AISI 303 |
Tightening torque, housing screws | 1.8 Nm |
Current loading capacity | ≤ 200 mA, overload and short-circuit protected |
Rated operating voltage | 18,0 ... 31.6 V from AS-Interface |
UL File Number | E223772 |
Number/Type | 4 electronic outputs, PNP, overload and short-circuit proof |
Surge protection | U , U : Over voltage category III, safe isolated power supplies (PELV) |
Signal delay | < 1 ms (input/AS-Interface) |
Input current | ≤ 9 mA (limited internally) |
AS-Interface specification | V3.0 |
LED AUX | ext. auxiliary voltage U ; dual LED green/red green: voltage OK red: reverse voltage |
AS-Interface | EN 62026-2:2013 |
Slave type | A/B slave |
Required master specification | ≥ V3.0 |
LED IN | switching state (input); 4 LED yellow |
0 (unattenuated) | ≤ 3 mA |
1 (attenuated) | ≥ 5 mA |
Input | EN 61131-2:2007 |
Profile | S-7.A.7 |
IO code | 7 |
ID code | A |
ID1 code | 7 |
ID2 code | 7 |
D0 | IN1 O1 |
D1 | IN2 O2 |
D2 | IN3 O3 |
D3 | IN4 O4 |
P0 | Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings) |
P1 | Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings) |
P2 | Lead breakage outputs P2 = 0 lead breakage on P2 = 1 lead breakage off (default settings) |
P3 | not used |
Tightening torque, cable gland | 0.4 Nm |
LED AS-i/FAULT | Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: sensor supply i.e. overload or lead interruption outputs |
Auxiliary voltage (output) | 20 ... 30 V DC PELV |
LED OUT | switching state (output); 4 LED yellow/red yellow: output active red: output overload or lead interruption |
Input/Output | safe isolation, rated insulation voltage 40 V DC |
Output/AS-Interface | safe isolation, rated insulation voltage 40 V DC |