Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 34395 |
MTTF | 230 a |
Mission Time (T | 20 a |
Diagnostic Coverage (DC) | 0 % |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Degree of protection | IP67 |
Connection | Cable piercing method flat cable yellow/flat cable black inputs/outputs: M12 round connector |
Housing | PBT |
Mass | 200 g |
Relative humidity | 85 % , noncondensing |
Altitude | ≤ 2000 m above MSL |
Mounting | Mounting plate |
Protection class | III |
Current | 2 A per output 6 A total (TB ≤ 40 °C) 4 A total (TB ≤ 70 °C) |
Pollution degree | 3 |
Vibration resistance | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
Shock and impact resistance | 30 , 11 ms in 6 spatial directions 3 shocks 10 , 16 ms in 6 spatial directions 1000 shocks |
Rated operating current | ≤ 40 mA |
Emitted interference | EN 61000-6-4:2007 |
Noise immunity | EN 61000-6-2:2005 |
Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005 EN 61000-6-4:2007 |
Supply | from external auxiliary voltage U |
Fieldbus standard | EN 62026-2:2013 |
LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
Voltage | ≥ (U - 0.5 V) |
Climatic conditions | For indoor use only |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
UL File Number | E223772 |
Number/Type | 4 electronic outputs, PNP |
Surge protection | U , U : Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral |
AS-Interface specification | V3.0 |
LED AUX | ext. auxiliary voltage U ; dual LED green/red green: voltage OK red: reverse voltage |
AS-Interface | EN 62026-2:2013 |
Slave type | Standard slave |
Required master specification | ≥ V2.1 |
Profile | S-8.1 |
IO code | 8 |
ID code | 1 |
ID1 code | F |
ID2 code | E |
D0 | - OUT1 |
D1 | - OUT2 |
D2 | - OUT3 |
D3 | - OUT4 |
P0 | communication monitoring P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition |
P1 | not used |
P2 | Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings) |
P3 | not used |
Tightening torque, cable gland | 0.4 Nm |
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: Output supply overload |
Auxiliary voltage (output) | 24 V DC ± 15 % PELV |
LED OUT | Switching status (output); 4 yellow/red LEDs Yellow: output active Red: output overload |