Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 13610 |
MTTF | 960 a |
Mission Time (T | 20 a |
Diagnostic Coverage (DC) | 0 % |
Operating voltage | 10 ... 60 V DC |
No-load supply current | ≤ 20 mA |
Switching frequency | 0 ... 80 Hz |
UL approval | cULus Listed, General Purpose |
CCC approval | Certified by China Compulsory Certification (CCC) |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Degree of protection | IP67 |
Time delay before availability | ≤ 30 ms |
Voltage drop | ≤ 3 V |
Operating current | 0 ... 200 mA |
Output type | 3-wire |
Switching function | Normally open (NO) |
Rated operating distance | 50 mm |
Installation | flush |
Output polarity | DC |
Assured operating distance | 0 ... 40.5 mm |
Reverse polarity protection | reverse polarity protected |
Switching state indicator | LED, yellow |
CSA approval | cCSAus Listed, General Purpose |
Connection type | Connector plug M12 x 1 , 4-pin |
Housing material | PBT |
Sensing face | PBT |
Hysteresis | typ. 3 % |
Off-state current | 0 ... 0.5 mA |
Standards | EN 50281-1-1 Protection via housing Use is restricted to the following stated conditions |
CE marking | [*PD-Z02586A*] |
Operating voltage indicator | LED, green |
ATEX marking | II 3D IP67 T 95 °C (203 °F) X |
Use in the hazardous area | see instruction manuals |
Category | 3G; 3D |
General | The apparatus has to be operated according to the appropriate data in the data sheet and in this instruction manual. The maximum surface temperature has been determined in accordance with method A without a dust layer on the equipment. The data stated in the data sheet are restricted by this operating instruction! The special conditions must be adhered to! |
Housing base | PBT |
Reduction factor r | 0.83 |
Maximum operating current I | The maximum permissible load current must be restricted to the values given in the following list. High load currents and load short-circuits are not permitted. |
Maximum operating voltage U | The maximum permissible operating voltage UB max is restricted to the values in the following list. Tolerances are not permissible. |
Maximum permissible ambient temperature T | dependant of the load current I and the max. operating voltage U Information can be taken from the following list. |
at U | 56 °C (132.8 °F) |
Maximum heating (Temperature rise) | dependant of the load current I and the max. operating voltage U Information can be taken from the following list. The maximum surface temperature at maximum ambient temperature is given in the Ex identification of the apparatus. |