Inductive sensor NCN40+U1+N0-V1

Inductive sensor NCN40+U1+N0-V1
Inductive sensor NCN40+U1+N0-V1

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 13284
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • Comfort series
Параметр Значение
Общие характеристики
Артикул 13284
MTTF 2225 a
Mission Time (T 20 a
Diagnostic Coverage (DC) 0 %
Switching frequency 0 ... 100 Hz
CCC approval CCC approval / marking not required for products rated ≤36 V
Ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1.
Storage temperature -40 ... 100 °C (-40 ... 212 °F)
Degree of protection IP68
Output type 2-wire
Switching function Normally closed (NC)
Rated operating distance 40 mm
Installation non-flush
Assured operating distance 0 ... 32.4 mm
A 10 mm
Reverse polarity protection reverse polarity protected
Short-circuit protection yes
Switching state indicator LED, yellow
CSA approval cCSAus Listed, General Purpose
Connection type Connector plug M12 x 1 , 4-pin
Housing material PBT
Sensing face PBT
Hysteresis 1 ... 15 typ. 5 %
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions
EAC conformity TR CU 012/2011
CE marking [*PD-Z02585A*]
Control drawing 116-0451
Nominal voltage 8 V
NAMUR EN 60947-5-6:2000 IEC 60947-5-6:1999
ATEX marking II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
Appropriate type NCN40+U...+N0...
Effective internal capacitance max. 120 nF ; a cable length of 10 m is considered.
Effective internal inductance max. 130 µH ; a cable length of 10 m is considered.
Use in the hazardous area see instruction manuals
Category 1G; 2G; 1D
Measuring plate not detected min. 3 mA
Measuring plate detected ≤ 1 mA
Maximum permissible ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Reduction factor r 0.8
Ordinary Location E87056
Hazardous Location E501628