Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 13284 |
MTTF | 2225 a |
Mission Time (T | 20 a |
Diagnostic Coverage (DC) | 0 % |
Switching frequency | 0 ... 100 Hz |
CCC approval | CCC approval / marking not required for products rated ≤36 V |
Ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. |
Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
Degree of protection | IP68 |
Output type | 2-wire |
Switching function | Normally closed (NC) |
Rated operating distance | 40 mm |
Installation | non-flush |
Assured operating distance | 0 ... 32.4 mm |
A | 10 mm |
Reverse polarity protection | reverse polarity protected |
Short-circuit protection | yes |
Switching state indicator | LED, yellow |
CSA approval | cCSAus Listed, General Purpose |
Connection type | Connector plug M12 x 1 , 4-pin |
Housing material | PBT |
Sensing face | PBT |
Hysteresis | 1 ... 15 typ. 5 % |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions |
EAC conformity | TR CU 012/2011 |
CE marking | [*PD-Z02585A*] |
Control drawing | 116-0451 |
Nominal voltage | 8 V |
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
ATEX marking | II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label. |
Appropriate type | NCN40+U...+N0... |
Effective internal capacitance | max. 120 nF ; a cable length of 10 m is considered. |
Effective internal inductance | max. 130 µH ; a cable length of 10 m is considered. |
Use in the hazardous area | see instruction manuals |
Category | 1G; 2G; 1D |
Measuring plate not detected | min. 3 mA |
Measuring plate detected | ≤ 1 mA |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. |
Reduction factor r | 0.8 |
Ordinary Location | E87056 |
Hazardous Location | E501628 |