Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 41678 |
MTTF | 1660 a |
Mission Time (T | 20 a |
Diagnostic Coverage (DC) | 0 % |
Switching frequency | 0 ... 150 Hz |
CCC approval | CCC approval / marking not required for products rated ≤36 V |
Ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. |
Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
Degree of protection | IP66 / IP68 / IP69K |
Mass | 225 g |
Electromagnetic compatibility | NE 21:2007 |
Note | Tightening torque: 1.8 Nm (housing) |
Output type | 2-wire |
Switching function | Normally closed (NC) |
Rated operating distance | 30 mm |
Installation | non-flush |
Assured operating distance | 0 ... 24.3 mm |
Reverse polarity protection | reverse polarity protected |
Short-circuit protection | yes |
Switching state indicator | LED, yellow |
Connection type | screw terminals |
Housing material | PA |
Sensing face | PA |
Hysteresis | 1 ... 15 typ. 5 % |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions |
Core cross-section | up to 2.5 mm |
CE marking | [*PD-Z02586A*] |
Certificate | PF 13 CERT 2895 X |
Control drawing | 116-0451 |
Nominal voltage | 8 V |
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
ATEX marking | II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label. |
Appropriate type | NBN30-U.K-N0... |
Effective internal capacitance | max. 105 nF ; a cable length of 10 m is considered. |
Effective internal inductance | max. 300 µH ; a cable length of 10 m is considered. |
Use in the hazardous area | see instruction manuals |
Category | 1G; 2G; 3G; 1D |
Actual operating distance | 27 ... 33 mm typ. |
Measuring plate not detected | min. 3 mA |
Measuring plate detected | ≤ 1 mA |
Information for connection | A maximum of two conductors with the same core cross section may be mounted on one terminal connection! tightening torque 1.2 Nm + 10 % |
Minimum core cross-section | without wire end ferrule 0.5 mm , with connector sleeves 0.34 mm |
Maximum core cross-section | without wire end ferrule 2.5 mm , with connector sleeves 1.5 mm |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. |
Reduction factor r | 0.79 |
Ordinary Location | E87056 |
Hazardous Location | E501628 |
for Pi=34 mW, Ii=25 mA, T6 | 73 °C (163.4 °F) |
for Pi=34 mW, Ii=25 mA, T5 | 88 °C (190.4 °F) |
for Pi=34 mW, Ii=25 mA, T4-T1 | 100 °C (212 °F) |
for Pi=64 mW, Ii=25 mA, T6 | 66 °C (150.8 °F) |
for Pi=64 mW, Ii=25 mA, T5 | 81 °C (177.8 °F) |
for Pi=64 mW, Ii=25 mA, T4-T1 | 100 °C (212 °F) |
for Pi=169 mW, Ii=52 mA, T6 | 45 °C (113 °F) |
for Pi=169 mW, Ii=52 mA, T5 | 60 °C (140 °F) |
for Pi=169 mW, Ii=52 mA, T4-T1 | 89 °C (192.2 °F) |
for Pi=242 mW, Ii=76 mA, T6 | 30 °C (86 °F) |
for Pi=242 mW, Ii=76 mA, T5 | 45 °C (113 °F) |
for Pi=242 mW, Ii=76 mA, T4-T1 | 74 °C (165.2 °F) |