Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

Inductive sensor NBN30-U4K-N0-V1

Inductive sensor NBN30-U4K-N0-V1
Inductive sensor NBN30-U4K-N0-V1

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 41562
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • Sensor head bidirectional and rotatable
  • 30 mm non-flush
Параметр Значение
Общие характеристики
Артикул 41562
Switching frequency 0 ... 150 Hz
CCC approval CCC approval / marking not required for products rated ≤36 V
Ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1.
Storage temperature -40 ... 100 °C (-40 ... 212 °F)
Degree of protection IP68 / IP69K
Mass 225 g
Electromagnetic compatibility NE 21:2007
Note Tightening torque: 1.8 Nm (housing)
Output type 2-wire
Switching function Normally closed (NC)
Rated operating distance 30 mm
Installation non-flush
Assured operating distance 0 ... 24.3 mm
Reverse polarity protection yes
Short-circuit protection yes
Switching state indicator LED, yellow
Connection type Connector plug M12 x 1 , 4-pin
Housing material PA/metal
Sensing face PA
Hysteresis typ. 5 %
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions
CE marking [*PD-Z02586A*]
Certificate PF 13 CERT 2895 X
Control drawing 116-0451
Nominal voltage 8 V
NAMUR EN 60947-5-6:2000 IEC 60947-5-6:1999
ATEX marking II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
Appropriate type NBN30-U.K-N0...
Effective internal capacitance max. 105 nF ; a cable length of 10 m is considered.
Effective internal inductance max. 300 µH ; a cable length of 10 m is considered.
Use in the hazardous area see instruction manuals
Category 1G; 2G; 3G
Actual operating distance 27 ... 33 mm typ. 30 mm
Measuring plate not detected min. 2.2 mA
Measuring plate detected ≤ 1 mA
Maximum permissible ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Reduction factor r 0.74
Ordinary Location E87056
Hazardous Location E501628
for Pi=34 mW, Ii=25 mA, T6 73 °C (163.4 °F)
for Pi=34 mW, Ii=25 mA, T5 88 °C (190.4 °F)
for Pi=34 mW, Ii=25 mA, T4-T1 100 °C (212 °F)
for Pi=64 mW, Ii=25 mA, T6 66 °C (150.8 °F)
for Pi=64 mW, Ii=25 mA, T5 81 °C (177.8 °F)
for Pi=64 mW, Ii=25 mA, T4-T1 100 °C (212 °F)
for Pi=169 mW, Ii=52 mA, T6 45 °C (113 °F)
for Pi=169 mW, Ii=52 mA, T5 60 °C (140 °F)
for Pi=169 mW, Ii=52 mA, T4-T1 89 °C (192.2 °F)
for Pi=242 mW, Ii=76 mA, T6 30 °C (86 °F)
for Pi=242 mW, Ii=76 mA, T5 45 °C (113 °F)
for Pi=242 mW, Ii=76 mA, T4-T1 74 °C (165.2 °F)

Техподдержка

Опишитите свой вопрос, специалист службы технической поддержки свяжется с Вами в течении нескольких часов

Отправляя заявку, вы принимаете условия Политики конфиденциальности.

Спасибо!

Ваше сообщение успешно отправлено