| Параметр | Значение |
| Общие характеристики | |
| Артикул | 39424 |
| MTTF | 3010 a |
| Mission Time (T | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Switching frequency | 0 ... 1500 Hz |
| CCC approval | CCC approval / marking not required for products rated ≤36 V |
| Ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. |
| Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
| Degree of protection | IP67 |
| Electromagnetic compatibility | NE 21:2007 |
| Bending radius | > 10 x cable diameter |
| Output type | 2-wire |
| Cable diameter | 4.8 mm ± 0.2 mm |
| Switching function | Normally closed (NC) |
| Rated operating distance | 4 mm |
| Installation | flush |
| Assured operating distance | 0 ... 3.24 mm |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | yes |
| Switching state indicator | all direction LED, yellow |
| CSA approval | cCSAus Listed, General Purpose |
| Connection type | cable PVC , 10 m |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Hysteresis | 1 ... 15 typ. 5 % |
| Standards | EN 50281-1-1 Protection via housing Use is restricted to the following stated conditions |
| Core cross-section | 0.34 mm |
| EAC conformity | TR CU 012/2011 |
| CE marking | [*PD-Z02585A*] |
| Scope of delivery | 2 self locking nuts in scope of delivery |
| Certificate | PF 13 CERT 2895 X |
| Control drawing | 116-0452 |
| Nominal voltage | 8 V |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| ATEX marking | II 3D IP67 T 111 °C (231.8 °F) X |
| Appropriate type | NCB4-12GM...-N0... |
| Effective internal capacitance | max. 120 nF A cable length of 10 m is considered. |
| Effective internal inductance | max. 50 µH ; a cable length of 10 m is considered. |
| Use in the hazardous area | see instruction manuals |
| Category | 1G; 2G; 3G; 1D |
| Effective internal capacitance C | max. 120 nF ; a cable length of 10 m is considered. |
| Effective internal inductance L | max. 50 µH ; A cable length of 10 m is considered. |
| General | The apparatus has to be operated according to the appropriate data in the data sheet and in this instruction manual. The data stated in the data sheet are restricted by this operating instruction! The special conditions must be observed! The ATEX Directive applies only to the use of apparatus under atmospheric conditions. If you use the device outside atmospheric conditions, consider that the permissible safety parameters should be reduced. |
| Actual operating distance | 3.6 ... 4.4 mm typ. |
| Measuring plate not detected | min. 2.2 mA |
| Measuring plate detected | ≤ 1 mA |
| Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the surface temperature, and the effective internal reactance values can be found on the EC-type-examination certificate. |
| Standard conformity | EN 60079-15:2003 Ignition protection category "n" Use is restricted to the following stated conditions |
| Reduction factor r | 0.78 |
| Ordinary Location | E87056 |
| Hazardous Location | E501628 |
| for Pi=34 mW, Ii=25 mA, T6 | 74 °C (165.2 °F) |
| for Pi=34 mW, Ii=25 mA, T5 | 89 °C (192.2 °F) |
| for Pi=34 mW, Ii=25 mA, T4-T1 | 100 °C (212 °F) |
| for Pi=64 mW, Ii=25 mA, T6 | 69 °C (156.2 °F) |
| for Pi=64 mW, Ii=25 mA, T5 | 84 °C (183.2 °F) |
| for Pi=64 mW, Ii=25 mA, T4-T1 | 100 °C (212 °F) |
| for Pi=169 mW, Ii=52 mA, T6 | 51 °C (123.8 °F) |
| for Pi=169 mW, Ii=52 mA, T5 | 66 °C (150.8 °F) |
| for Pi=169 mW, Ii=52 mA, T4-T1 | 74 °C (165.2 °F) |
| for Pi=242 mW, Ii=76 mA, T6 | 39 °C (102.2 °F) |
| for Pi=242 mW, Ii=76 mA, T5 | 52 °C (125.6 °F) |
| for Pi=242 mW, Ii=76 mA, T4-T1 | 52 °C (125.6 °F) |
| at U | 11 K |
| Maximum heating (Temperature rise) | Values can be obtained from the following list, depending on the max. operating voltage Ub max and the minimum series resistance Rv. |
| using an amplifier in accordance with EN 60947-5-6 | 11 K |