| Параметр | Значение |
| Общие характеристики | |
| Артикул | 32435 |
| MTTF | 1870 a |
| Mission Time (T | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Switching frequency | 0 ... 200 Hz |
| CCC approval | CCC approval / marking not required for products rated ≤36 V |
| Ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. |
| Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
| Degree of protection | IP66 / IP67 |
| Electromagnetic compatibility | NE 21:2007 |
| Bending radius | > 10 x cable diameter |
| Output type | 2-wire |
| Cable diameter | 6 mm ± 0.2 mm |
| Switching function | Normally closed (NC) |
| Rated operating distance | 10 mm |
| Installation | flush |
| Assured operating distance | 0 ... 8.1 mm |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | yes |
| Switching state indicator | all direction LED, yellow |
| CSA approval | cCSAus Listed, General Purpose |
| Connection type | cable PVC , 2 m |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Hysteresis | 1 ... 15 typ. 5 % |
| Standards | EN 60079-0:2012+A11:2013, EN 60079-31:2014 Protection by enclosure "tc" Some of the information in this instruction manual is more specific than the information provided in the datasheet. |
| Core cross-section | 0.75 mm |
| EAC conformity | TR CU 012/2011 |
| CE marking | [*PD-Z02585A*] |
| Certificate | PF 13 CERT 2895 X |
| Control drawing | 116-0452 |
| Nominal voltage | 8 V |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| ATEX marking | II 3D Ex tc IIIC T80°C Dc The Ex-related marking can also be printed on the enclosed label. |
| Appropriate type | NCB10-30GM...-N0... |
| Effective internal capacitance | max. 105 nF ; a cable length of 10 m is considered. |
| Effective internal inductance | max. 100 µH ; a cable length of 10 m is considered. |
| Use in the hazardous area | see instruction manuals |
| Category | 1G; 2G; 3G; 1D; 3D |
| Effective internal capacitance C | max. 105 nF ; a cable length of 10 m is considered. |
| Effective internal inductance L | max. 100 µH ; A cable length of 10 m is considered. |
| General | The corresponding datasheets, declarations of conformity, EC-type examination certificates, certifications, and control drawings, where applicable (see datasheets), form an integral part of this document. These documents can be found at www.pepperl-fuchs.com. The maximum surface temperature of the device was determined without a layer of dust on the apparatus. Some of the information in this instruction manual is more specific than the information provided in the datasheet. |
| Actual operating distance | 9 ... 11 mm typ. |
| Measuring plate not detected | min. 2.2 mA |
| Measuring plate detected | ≤ 1 mA |
| Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the surface temperature, and the effective internal reactance values can be found on the EC-type-examination certificate. |
| Standard conformity | EN 60079-15:2005 Ignition protection category "n" Use is restricted to the following stated conditions |
| Reduction factor r | 0.75 |
| Ordinary Location | E87056 |
| Hazardous Location | E501628 |
| for Pi=34 mW, Ii=25 mA, T6 | 55 °C (131 °F) |
| for Pi=34 mW, Ii=25 mA, T5 | 55 °C (131 °F) |
| for Pi=34 mW, Ii=25 mA, T4-T1 | 55 °C (131 °F) |
| for Pi=64 mW, Ii=25 mA, T6 | 55 °C (131 °F) |
| for Pi=64 mW, Ii=25 mA, T5 | 55 °C (131 °F) |
| for Pi=64 mW, Ii=25 mA, T4-T1 | 55 °C (131 °F) |
| for Pi=169 mW, Ii=52 mA, T6 | 52 °C (125.6 °F) |
| for Pi=169 mW, Ii=52 mA, T5 | 52 °C (125.6 °F) |
| for Pi=169 mW, Ii=52 mA, T4-T1 | 52 °C (125.6 °F) |
| for Pi=242 mW, Ii=76 mA, T6 | 44 °C (111.2 °F) |
| for Pi=242 mW, Ii=76 mA, T5 | 44 °C (111.2 °F) |
| for Pi=242 mW, Ii=76 mA, T4-T1 | 44 °C (111.2 °F) |
| Maximum permissible ambient temperature T | Values can be obtained from the following list, depending on the max. operating voltage Ub max and the minimum series resistance Rv. |
| at U | 66 °C (150.8 °F) |
| using an amplifier in accordance with EN 60947-5-6 | 66 °C (150.8 °F) |