Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

Inductive slot sensor SJ5-K-N 2864

Inductive slot sensor SJ5-K-N

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 2864
Под заказ
Запрос цены

Цены носят информационный характер и не являются публичной офертой. Точную цену и срок поставки подтвердит менеджер при оформлении заявки

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • 5 mm slot width
Параметр Значение
Общие характеристики
Артикул 2864
Slot width 5 mm
MTTF 4560 a
Mission Time (T 20 a
Diagnostic Coverage (DC) 0 %
Operating voltage 5 ... 25 V
Switching frequency 0 ... 2000 Hz
UL approval cULus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Degree of protection IP67
Bending radius > 10 x cable diameter
Output type 2-wire
Switching function Normally closed (NC)
CSA approval cCSAus Listed, General Purpose
Connection type cable PVC , 2 m
Housing material PBT
Hysteresis 0.05 ... 0.3 mm
Standards EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions
Core cross-section 0.75 mm
CE marking [*PD-Z02585A*]
Control drawing 116-0453
Nominal voltage 8.2 V (R approx. 1 kΩ)
NAMUR EN 60947-5-6:2000 IEC 60947-5-6:1999
ATEX marking II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
Appropriate type SJ5-K...
Effective internal capacitance max. 50 nF ; a cable length of 10 m is considered.
Effective internal inductance max. 550 µH ; a cable length of 10 m is considered.
Use in the hazardous area see instruction manuals
Category 1G; 2G; 1D
Measuring plate not detected ≥ 3 mA at nominal voltage
Measuring plate detected ≤ 1 mA at nominal voltage
Highest permissible ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1.
Maximum permissible ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
Ordinary Location E87056
Hazardous Location E501628
Depth of immersion (lateral) 8 ... 10 mm , typ. 9 mm

Техподдержка

Опишитите свой вопрос, специалист службы технической поддержки свяжется с Вами в течении нескольких часов

Отправляя заявку, вы принимаете условия Пользовательского соглашения.

Спасибо!

Ваше сообщение успешно отправлено