Пт-Пн: 9:00 - 18:00

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Цены носят информационный характер и не являются публичной офертой. Точную цену и срок поставки подтвердит менеджер при оформлении заявки
Доставка в любой регион России транспортной
компанией на Ваш выбор
| Параметр | Значение |
| Общие характеристики | |
| Артикул | 2665 |
| Slot width | 3.5 mm |
| MTTF | 8415 a |
| Mission Time (T | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Operating voltage | 5 ... 25 V |
| Switching frequency | 0 ... 3000 Hz |
| UL approval | cULus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated ≤36 V |
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
| Degree of protection | IP67 |
| Output type | 2-wire |
| Switching function | Normally closed (NC) |
| CSA approval | cCSAus Listed, General Purpose |
| Connection type | flexible leads LiY , 500 mm |
| Housing material | PBT/PPS |
| Hysteresis | 0.41 ... 0.6 mm |
| Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions |
| Core cross-section | 0.14 mm |
| EAC conformity | TR CU 012/2011 |
| CE marking | [*PD-Z02585A*] |
| Control drawing | 116-0453 |
| Nominal voltage | 8.2 V (R approx. 1 kΩ) |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| ATEX marking | II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label. |
| Appropriate type | SJ3,5-...-N... |
| Effective internal capacitance | max. 50 nF ; a cable length of 10 m is considered. |
| Effective internal inductance | max. 250 µH ; a cable length of 10 m is considered. |
| Use in the hazardous area | see instruction manuals |
| Category | 1G; 2G; 1D |
| Measuring plate not detected | ≥ 3 mA at nominal voltage |
| Measuring plate detected | ≤ 1 mA at nominal voltage |
| Highest permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. |
| Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. |
| Ordinary Location | E87056 |
| Hazardous Location | E501628 |
| Suitable for 21 technology | yes , Reverse polarity protection diode not required |
| Depth of immersion (lateral) | 5 ... 7 mm , typ. 6 mm |