  • 50 mm non-flush
Параметр Значение
Общие характеристики
Артикул 10198
MTTF 11400 a
Mission Time (T 20 a
Diagnostic Coverage (DC) 0 %
Switching frequency 0 ... 100 Hz
CCC approval CCC approval / marking not required for products rated ≤36 V
Ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1.
Degree of protection IP67
Note Tightening torque: 1.8 Nm (housing)
Output type 2-wire
Switching function Normally closed (NC)
Rated operating distance 50 mm
Installation non-flush
Assured operating distance 0 ... 40.5 mm
CSA approval cCSAus Listed, General Purpose
Connection type screw terminals
Housing material PBT
Sensing face PBT
Standards EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions
Core cross-section up to 2.5 mm
CE marking [*PD-Z02585A*]
Control drawing 116-0451
Nominal voltage 8.2 V (R approx. 1 kΩ)
NAMUR EN 60947-5-6:2000 IEC 60947-5-6:1999
ATEX marking II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
Appropriate type NJ 50-FP-N...
Effective internal capacitance max. 320 nF ; a cable length of 10 m is considered.
Effective internal inductance max. 360 µH ; a cable length of 10 m is considered.
Use in the hazardous area see instruction manuals
Category 1G; 2G; 1D
Measuring plate not detected ≥ 3 mA
Measuring plate detected ≤ 1 mA
Information for connection A maximum of two conductors with the same core cross section may be mounted on one terminal connection! tightening torque 1.2 Nm + 10 %
Minimum core cross-section without wire end ferrule 0.5 mm , with connector sleeves 0.34 mm
Maximum core cross-section without wire end ferrule 2.5 mm , with connector sleeves 1.5 mm
Maximum permissible ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Reduction factor r 0.85
Ordinary Location E87056
Hazardous Location E501628