| Параметр | Значение |
| Общие характеристики | |
| Артикул | 10192 |
| MTTF | 9191 a |
| Mission Time (T | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Switching frequency | 0 ... 100 Hz |
| UL approval | cULus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated ≤36 V |
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
| Degree of protection | IP68 |
| Note | only for non-ferrous metal |
| Output type | 2-wire |
| Type of protection | intrinsic safety |
| Switching function | Normally open (NO) |
| Rated operating distance | 6 mm |
| Installation | flush |
| Assured operating distance | 0 ... 4.86 mm |
| CSA approval | cCSAus Listed, General Purpose |
| Connection type | screw terminals |
| Housing material | PBT |
| Sensing face | PBT |
| Standards | IEC 60079-0:2011 , IEC 60079-11:2011 |
| Core cross-section | up to 2.5 mm |
| CE marking | [*PD-Z02585A*] |
| Safety Integrity Level (SIL) | SIL 3 |
| Control drawing | 116-0454 |
| IECEx certificate | IECEx PTB 11.0092X |
| IECEx marking | Ex ia I Mb |
| Nominal voltage | 8.2 V (R approx. 1 kΩ) |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| ATEX marking | II 1D Ex ia IIIC T135°C Da |
| Appropriate type | NJ6S1+U.+N... |
| Effective internal capacitance | max. 180 nF A cable length of 10 m is considered. |
| Effective internal inductance | max. 150 µH A cable length of 10 m is considered. |
| Use in the hazardous area | see instruction manuals |
| Measuring plate not detected | ≤ 1 mA |
| Measuring plate detected | ≥ 3 mA |
| Information for connection | A maximum of two conductors with the same core cross section may be mounted on one terminal connection! tightening torque 1.2 Nm + 10 % |
| Minimum core cross-section | without wire end ferrule 0.5 mm , with connector sleeves 0.34 mm |
| Maximum core cross-section | without wire end ferrule 2.5 mm , with connector sleeves 1.5 mm |
| Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at U = 16 V , I = 25 mA , P = 34 mW : 100 °C (212 °F) at U = 16 V , I = 25 mA , P = 64 mW : 100 °C (212 °F) at U = 16 V , I = 52 mA , P = 169 mW : 80 °C (176 °F) at U = 16 V , I = 76 mA , P = 242 mW : 61 °C (141.8 °F) |
| Equipment protection level | Ga , Gb , Da , Mb |
| ATEX certificate | PTB 00 ATEX 2049 X |
| Reduction factor r | 0 |
| Ordinary Location | E87056 |
| Hazardous Location | E501628 |
| for ATEX | at U = 16 V , I = 25 mA , P = 34 mW , T6 : 57 °C (134.6 °F) T5 : 69 °C (156.2 °F) T4 : 97 °C (206.6 °F) T3 : 97 °C (206.6 °F) T2 : 97 °C (206.6 °F) T1 : 97 °C (206.6 °F) at U = 16 V , I = 25 mA , P = 64 mW , T6 : 52 °C (125.6 °F) T5 : 64 °C (147.2 °F) T4 : 92 °C (197.6 °F) T3 : 92 °C (197.6 °F) T2 : 92 °C (197.6 °F) T1 : 92 °C (197.6 °F) at U = 16 V , I = 52 mA , P = 169 mW , T6 : 34 °C (93.2 °F) T5 : 46 °C (114.8 °F) T4 : 74 °C (165.2 °F) T3 : 74 °C (165.2 °F) T2 : 74 °C (165.2 °F) T1 : 74 °C (165.2 °F) at U = 16 V , I = 76 mA , P = 242 mW , T6 : 22 °C (71.6 °F) T5 : 34 °C (93.2 °F) T4 : 61 °C (141.8 °F) T3 : 61 °C (141.8 °F) T2 : 61 °C (141.8 °F) T1 : 61 °C (141.8 °F) |
| for IECEx | at U = 16 V , I = 25 mA , P = 34 mW , T6 : 73 °C (163.4 °F) T5 : 88 °C (190.4 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at U = 16 V , I = 25 mA , P = 64 mW , T6 : 69 °C (156.2 °F) T5 : 84 °C (183.2 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at U = 16 V , I = 52 mA , P = 169 mW , T6 : 51 °C (123.8 °F) T5 : 66 °C (150.8 °F) T4 : 80 °C (176 °F) T3 : 80 °C (176 °F) T2 : 80 °C (176 °F) T1 : 80 °C (176 °F) at U = 16 V , I = 76 mA , P = 242 mW , T6 : 39 °C (102.2 °F) T5 : 54 °C (129.2 °F) T4 : 61 °C (141.8 °F) T3 : 61 °C (141.8 °F) T2 : 61 °C (141.8 °F) T1 : 61 °C (141.8 °F) |