Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 83562 |
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) Observe the temperature range limited by derating, see section derating. |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Degree of protection | IP20 |
Connection | protected area: terminals 3, 4 unprotected area: terminals 1, 2 |
Mass | approx. 20 g |
Relative humidity | max. 95 % , without condensation |
Mounting | pluggable in base module for mounting on 35 mm DIN mounting rail |
Current | 500 mA , restrictions see derating characteristics |
Marking | II 2(1)G Ex ia [ia Ga] IIC T6...T4 Gb II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
Dimensions | 6.2 x 77 x 79 mm |
EU-type examination certificate | BVS 17 ATEX E 069 X |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Designation | system components: - base module with screw terminals M-LB-Ex-5000 - base module with spring terminals M-LB-Ex-5000.SP - universal power rail M-UPR-03-S - place holder module M-LB-Ex-5900 - separation wall M-UPR-I |
Rated current | 500 mA , restrictions see derating characteristics |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 |
Temperature class | T6 for ambient temperature ≤ 60 °C T5 for ambient temperature ≤ 70 °C T4 for ambient temperature ≤ 80 °C |
Safety Integrity Level (SIL) | SIL 3 |
IECEx certificate | IECEx BVS 17.0061X |
IECEx marking | Ex ia [ia Ga] IIC T6...T4 Gb [Ex ia Da] IIIC [Ex ia Ma] I |
Voltage | 30 V |
Nominal voltage | 24 V DC |
Functional safety | IEC/EN 61508:2010 |
Internal capacitance | negligible |
Internal inductance | 36 µH |
Insertion loss | ≤ 0.04 dB, at 0 ... 4 kHz, in 600 Ω-System ≤ 3 dB, at 0 ... 500 kHz, in 100 Ω-System |
Number of protected signal lines | 2 |
Leakage current | < 6 µA at 24 V and 25 °C (77 °F) , line-line |
Total discharge current (8/20 µs) | 20 kA (1x) |
Maximum continuous operating voltage | 30 V DC |
Nominal discharge current (8/20 µs) | 5 kA per line (10x) |
Voltage protection level | max. 45 V line-line for nominal discharge current I max. 60 V line-earth for nominal discharge current I |
Topology | grounded |
Series resistance | ≤ 0.6 Ω per line |
Impulse rating | 1 kV/0.5 kA (category C1) 10 kV/5 kA (category C2) 1 kA (category D1) |
Impulse discharge current (10/350 µs) | 1 kA per line (2x) |
Impulse reset time | < 500 ms |
Surge protective devices for low voltage | EN 61643-21:2001+A1:2009+A2:2013 IEC 61643-21:2001+A1:2008+A2:2012 |
Rated surge current (8/20 µs) | 10 kA per line (1x) |