Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

Power supply LB9006C

Power supply LB9006C
Power supply LB9006C

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 59349
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • Power supply for 24 V
  • Permits vertical or horizontal mounting in Zone 2
  • Use three power supplies for redundancy
  • Galvanic isolation to mains
  • Supply of I/O modules and com units
  • Mounting in Zone 2, Class I/Div.2 or in the safe area
Параметр Значение
Общие характеристики
Артикул 59349
UL approval E106378
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Degree of protection IP20 (module) , mounted on backplane
Mass approx. 220 g
Power consumption max. 30 W for Zone 2 applications max. 45 W for applications in safe area parallel connection with other LB9006C (autom. power sharing)
Electromagnetic compatibility NE 21
Marking II 3 G Ex nA IIC T4 Gc
Vibration resistance frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Dimensions 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
LED indicator Power LED (P) green: OFF in case of loss of 24 V or 12 V or 5 V
IECEx approval BVS 09.0037X
Approved for Ex nA IIC T4 Gc
Power P ≤ 5.4 W, P ≤ 25 W - P for Zone 2 applications P ≤ 5.4 W, P ≤ 39 W - P for applications in safe area
Inrush current 1.5 A (10 ms)
Directive 2014/30/EU EN 61326-1
Shock resistance shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Certificate PF 08 CERT 1234 X
Directive 2014/34/EU EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010
Power dissipation approx. 15 % of power consumption
Voltage 5.4 V DC +/- 5% , 12 V DC + 4/- 2%
Maximum safe voltage 60 V DC (SELV/PELV)
Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Lloyd Register 15/20021
Bureau Veritas Marine 22449/B0 BV
DNV GL Marine TAA0000034
Output/power supply, internal bus EN 60950-1 (Safety requirement: < 60 V, external supply SELV/PELV)
Bus coupler 2
I/O modules >12, depending on the type
Input voltage range 18 ... 32 V DC (SELV/PELV)

Техподдержка

Опишитите свой вопрос, специалист службы технической поддержки свяжется с Вами в течении нескольких часов

Отправляя заявку, вы принимаете условия Политики конфиденциальности.

Спасибо!

Ваше сообщение успешно отправлено