Параметр | Значение |
Общие характеристики | |
Артикул | 40024 |
UL approval | E106378 |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Degree of protection | IP20 (module) , mounted on backplane |
Connection | via backplane |
Mass | approx. 150 g |
Rated voltage | 5 V DC , only in connection with the power supplies LB9*** |
Power consumption | 2 W |
Electromagnetic compatibility | NE 21 |
Marking | II 3 G Ex nA IIC T4 Gc |
Protocol | H1 to IEC 1158-2 |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) |
LED indicator | LED 1 (power supply): On = operating, fast flash = cold start LED 2 (collective alarm): On = internal fault, flashing = no fieldbus LED 3 (operating mode): Flashing = active |
IECEx approval | BVS 09.0037X |
EAC approval | Russia: RU C-IT.MIII06.B.00129 |
Approved for | Ex nA IIC T4 Gc |
Directive 2014/30/EU | EN 61326-1 |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Certificate | PF 08 CERT 1234 X |
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 |
Control drawing | 116-0321 |
Fieldbus type | FOUNDATION Fieldbus H1 |
ATEX approval | PF 08 CERT 1234 X |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Baud rate | 31.25 kBit/s , MBP |
Lloyd Register | 15/20021 |
Bureau Veritas Marine | 22449/B0 BV |
American Bureau of Shipping | T1450280/UN |
DNV GL Marine | TAA0000034 |
Number of stations per bus line | 1 or 2, depending on the required response times |
Supported I/O modules | 5 slots, to be filled with (combinations possible): 1*08 digital input, 8-channel, NAMUR 3*05 analog input, 4-channel, 20 mA (HART via service bus) 4*05 analog output, 4-channel, 20 mA (HART via service bus) 5*04 Pt100 RTD input, 4-channel 5*05 thermocouple input, 4-channel 6005 relay output, 4-channel, 230 V 6006 relay output, 8-channel, 24 V 6*08 digital output, 8-channel, Ex i 6*10-6*15 digital output, 4-channel, Ex i power * = variable (0=non-IS, 1=IS) |
Bus length | max. 1900 m (must not be exceeded by the sum of all trunk and spur lines) |
Addressing | via PCS (software) |
Station connection | directly at the trunk or via spur protector |
Number of channels per station | max. 20 analog, max. 40 digital |
Auxiliary energy | 24 V DC Trunk load 20 mA |
Spur length | max. 120 m (depending on the number of field devices. Modular I/O station = 1 field device) |